The Bosch D1256RB Fire VDF Keypad is a full-function system controller and annunciator with a 16-character vacuum fluorescent display, four function keys…
The Bosch D1256RB Fire VDF Keypad serves as a full-function system controller and annunciator for fire alarm systems. It features a 16-character vacuum fluorescent display (VFD) that shows system status using words, numbers, and symbols, along with four LEDs indicating fire, silenced, supervisory, and trouble conditions. Four one-touch function keys allow users to silence audible alarms, silence trouble sounders, reset the annunciator display, and reset system detectors, while four navigational keys provide access to programmed system functions.
The keypad is compatible with D9412GV2, D9124GV2, and D7412GV2 control panels running firmware 7.02 or higher. It mounts on a surface using a D56 or D56R Conduit Back Box, or on a desk with a D55 Desk Stand. The unit operates on 12 VDC from the control panel, drawing 104–225 mA, and meets UL standards including UL1610, UL365, UL1076, UL1023, UL864 9th edition, and UL985. Environmental ratings cover 0°C to 50°C and 5–85% relative humidity.
| Relative Humidity | 5% to 85% non‑condensing at +30°C (+86°F) |
|---|---|
| Operating Temperature | 0°C to +50°C (+32°F to +122°F) |
| Color | Red |
| Dimensions | 11.7 cm x 21 cm x 2 cm (4.6 in. x 8.2 in. x 0.8 in.) |
| Material | CHI MEI POLYLAC® PA757 ABS with UV Stabilizer, UL94-HB Fire Rated |
| Current Draw | 104 mA minimum, 225 mA maximum |
| Voltage | 12 VDC nominal supplied by the control panel |
The D1256RB is compatible with D9412GV2, D9124GV2, and D7412GV2 control panels with firmware version 7.02 or higher.
The keypad requires 12 VDC nominal supplied by the control panel, with a current draw of 104 mA minimum to 225 mA maximum.
It is listed under UL1610, UL365, UL1076, UL1023, UL864 9th edition, and UL985.