Technical manual for the Bell & Gossett TES-375B steam heating system covering basics, components, installation, service and troubleshooting.
This manual provides an overview of steam heating fundamentals, system components, boiler operation, and control devices for the TES-375B. It explains pressure‑drop calculations, safety factors, and sizing guidelines for both small and larger installations.\n\nThe document also details the various steam system types (one‑pipe, two‑pipe, up‑feed, down‑feed), condensate handling equipment, deaerating heaters, service procedures, and a troubleshooting guide to help technicians diagnose and resolve common issues.
| Maximum working pressure | 15 psig |
|---|---|
| Typical pressure drop for small systems | 1/8 psi |
| Dimension A total height for small systems | 14.0 in water |
Small systems are sized for a pressure drop of 1/8 psi for both the steam and condensate piping.
The steam boilers are low‑pressure types with a maximum working pressure of 15 psig.