About this manual

The RemoDAQ-8017B+ is an 8‑channel analog input module with optional differential or single‑ended configurations, designed for RS‑485 networks and Modbus communication. It provides high‑precision 24‑bit ADC conversion, isolated inputs, and a range of programmable settings.

The manual details terminal distribution, wiring instructions, default and jumper settings, calibration procedures, command syntax, and application notes such as the INIT mode for restoring factory configuration. This manual is written in Chinese.

What's inside

  • Overview
  • Terminal Distribution
  • Features
  • Block Diagram
  • Wiring Instructions
  • Default Settings
  • Jumper Settings
  • Calibration
  • Settings List
  • Commands

Specifications

Input channels8 differential or 6 differential + 2 single‑ended
Input typesmV, V, mA
Input range±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 4‑20 mA
Over‑voltage protection±35 V
Sampling frequency10 samples/s
Bandwidth13.1 Hz
Input impedance20 MΩ
Zero drift±6 µV/°C
Full‑scale drift±25 ppm/°C
CMRR (50/60 Hz)92 dB
Power consumption1.2 W @ 24 VDC
Isolation voltage3000 VDC
Operating temperature-20 °C to 70 °C
Humidity range5 % to 90 % (no condensation)

Frequently asked questions

What is the default baud rate of the RemoDAQ-8017B+?

The default baud rate is 9600 bps.

How many analog input channels does the RemoDAQ-8017B+ support?

It supports up to 8 analog input channels, configurable as 8 differential or 6 differential plus 2 single‑ended channels.

What isolation voltage does the module provide?

The module provides 3000 VDC isolation voltage.

How can the INIT mode be activated?

Short the INIT* terminal to GND, then send the command $002 at 9600 bps; the module will force Address = 00 and baudrate = 9600.