BEAMA Guide to RCD Protection of EV Charging Installations

A practical guide for designers and installers on selecting Residual Current Devices (RCDs) and using RDC-DDs for Electric Vehicle charging installations.


BEAMA Guide to RCD Protection of EV Charging Installations - cover page
Brand
BEAMA
Category
Other Electronics
Document type
User Manual
Language
English
Pages
14
File format
PDF
File size
1.4 MB
Published
05 November, 2026
Updated
05 November, 2026
MD5 checksum
1B101E5E083A13C00EED5ECE9C5476B9

About this manual

This guide provides information on the selection and application of Residual Current Devices (RCDs) for the protection of electric vehicle (EV) charging installations. It covers the requirements for RCDs, the effects of DC fault currents on RCDs, and the use of RDC-DDs, RDC-MDs, and RDC-PDs in EV charging systems.

The document details specific regulations from BS 7671, including the need for Type A, Type B, or Type F RCDs, and explains how to handle DC fault currents exceeding 6 mA. It further classifies Residual Direct Current Detecting Devices (RDC-DDs) into RDC-MDs and RDC-PDs, describing their construction and application in Mode 3 charging scenarios.

What's inside

  • Introduction
  • Abbreviations and Definitions
  • RCD selection
  • Effects of DC fault currents on RCDs
  • RDC-DDs
  • RDC-MDs
  • RDC-PDs
  • RDC-DD testing
  • RCD protection for Electric Vehicle wireless power transfer

Frequently asked questions

What type of RCD is required for EV charging installations unless supplied by a circuit using electrical separation?

An RCD of at least Type A shall be provided.

What is the minimum DC fault current level that RCDs must protect against in EV charging installations?

Protection shall be provided against DC fault currents exceeding 6 mA.

What are the two types of RDC-DDs classified under BS IEC 62955?

RDC-MDs and RDC-PDs.