BA405C Intrinsically Safe 2-Wire 4-20mA Manual Set Point Station Instruction Manual

Manual for the BA405C intrinsically safe 2-wire 4/20mA set point station, covering hazardous-area design, installation, calibration, and maintenance.


BA405C Intrinsically Safe 2-Wire 4-20mA Manual Set Point Station Instruction Manual - cover page
Brand
BA
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
16
File format
PDF
File size
863 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
987A722F3CB726AC2E218E5D618DD554

About this manual

The BA405C is an intrinsically safe, loop-powered manual set point station that lets the current flowing in a 4/20mA loop be adjusted by hand from within a hazardous process area. Its main application is the adjustment of plant parameters: controller set points, actuator positions, or any other variable represented by a 4/20mA signal.

The station uses a ten-turn control for accurate adjustment of the loop current and has a 3½-digit indicator that can be calibrated on site to display the current in linear engineering units. Optional loop-powered (green) and separately powered (orange) display backlights are available. The unit is covered by EC-Type Examination Certificate ITS03ATEX21103 for Group II Category 1G apparatus, EEx ia IIC T5, and has FM intrinsic safety and nonincendive approval for use in the USA.

What's inside

  • Description
  • Operation
  • Intrinsic Safety Certification
  • System Design for Hazardous Areas
  • Installation
  • Calibration
  • Maintenance
  • Accessories

Specifications

Loop current adjustment rangeapproximately 3.5 to 21 mA
Display3½ digit indicator
Adjustment controlhigh resolution ten turn control
Operating voltage without options6.1 to 30 V
Operating voltage with loop powered backlight10 to 30 V
Maximum input voltage (Ui)30 V dc
Maximum input current (Ii)200 mA dc
Maximum input power (Pi)0.85 W
Equivalent internal capacitance / inductanceCi = 40 nF, Li = 0.01 mH
ATEX certificationGroup II Category 1G, EEx ia IIC T5

Frequently asked questions

What current range can the BA405C adjust?

The ten-turn control knob allows the loop current to be manually set at any value between approximately 3.5 and 21 mA.

Can the internal display show engineering units?

Yes. The 3½-digit indicator can be calibrated on site to show the loop current in engineering units, for example the requested speed in RPM for a speed controller.

What hazardous area approvals does the BA405C have?

It holds EC-Type Examination Certificate ITS03ATEX21103 for Group II Category 1G, EEx ia IIC T5, and has FM intrinsic safety and nonincendive approval for use in the USA.

Which backlight options are offered?

Two types are available: a loop-powered backlight giving green background illumination, and a separately powered backlight with a bright orange output.

Download PDF (863 KB)