B&R 2005 Temperature Module AT350/AT450 User's Manual

User manual for B&R 2005 AT350/AT450 PT100 temperature input modules, covering order data, technical data, pin assignments and converter values.


B&R 2005 Temperature Module AT350/AT450 User's Manual - cover page
Brand
BR
Category
Other Electronics
Document type
User Manual
Language
English
Pages
13
File format
PDF
File size
422 KB
Published
13 November, 2026
Updated
13 November, 2026
MD5 checksum
24699C3C0D72A2D44D75133A9A5F9887

About this manual

The AT350 and AT450 are temperature modules for PT100 temperature sensors in the B&R 2005 system. AT350 uses a 3-line connection and AT450 uses a 4-line connection; both provide four inputs with a measurement range of -50 to +450 °C.

The manual covers order data, technical data, status LEDs, pin assignments, input circuit diagrams, temperature-to-converter-value relationships, open line detection, variable declarations and mode register settings.

What's inside

  • General information
  • Order Data
  • Technical Data
  • Status LEDs
  • Pin Assignments
  • Input Circuit Diagram
  • Relationship between Temperature and Converter Value
  • Open Line Detection
  • Variable Declarations
  • Mode Register

Specifications

Number of inputs4 inputs for resistance measurement
Sensor type (AT350)PT100, 3-line connection, IEC/EN 60751
Sensor type (AT450)PT100, 4-line connection, IEC/EN 60751
Measurement range-50 to +450 °C
ResolutionInternal 13500 steps
Measuring time per channel20 or 16.67 ms
Conversion time (all channels)100 ms and 85 ms
Input filterBessel low pass 1st order
Measurement current2.5 mA (±0.2%)
DimensionsB&R 2005 single-width
LinearizationAutomatic in the module
C-UL-US listedYes

Frequently asked questions

Which PT100 connection types do AT350 and AT450 use?

AT350 uses a 3-line connection and AT450 uses a 4-line connection.

What is the measurement range?

The measurement range is -50 to +450 °C.

How can 50 Hz or 60 Hz mains hum be suppressed?

Set the measurement time to 20 ms for 50 Hz or 16.67 ms for 60 Hz.

How are open inputs or broken lines indicated?

Open inputs or broken sensor/sense lines are reported with converter values -32768 (8000) or +32767 (7FFF).