Technical manual for the Arteco SU112 axis controller with integrated PLC, covering hardware installation, power supply, connectors, signals and expansion…
The Arteco SU112 technical manual covers the principal hardware specifications of the Axis Controller with integrated PLC SU112 and the procedure for correct installation of the system. It states that calibration, configuration and maintenance procedures must be performed by specialized personnel.
The document describes installation and power supply, connectors and signals, connections and cables, unit layout, jumpers and LED functions, and expansion modules including 8 input/8 output, analog axis and CAN serial bus expansions. It also includes connection examples and diagrams and dimensions.
| Power supply voltage | 24 V dc ±20% |
|---|---|
| Current absorption, no load | 300 mA |
| Current absorption, encoder connected | 500 mA |
| Operational temperature | +5 °C to +40 °C |
| Storage temperature | -10 °C to +55 °C |
| Humidity | 30% to 90%, without condensation |
| Encoder power supply | 5 V, 300 mA max, fuse protected |
| Maximum external counting frequency | 200 kHz; 400 kHz option |
| Analog output | Differential ±10 V, 12-bit resolution |
| Analog input | 0 to 10 V common-mode range |
| Backup battery | 3.6 V CR2032 lithium, not rechargeable |
It requires 24 V dc through connector P1, with a maximum tolerance of ±20%.
The operational temperature range is +5 °C to +40 °C.
It accepts incremental encoders with Push-Pull or Line-Driver output at +5 V supplied by the unit.
It uses a non-rechargeable 3.6 V CR2032 lithium battery.