Installation manual for American Rotary 240V HD/CNC rotary phase converters with built-in starters, covering safety, wiring, grounding and voltage balance.
American Rotary's 240V HD/CNC rotary phase converter installation manual begins with safety instructions and warnings. It says installation must be performed by a licensed electrician, that the converter must be connected to a separate electrical circuit directly from the entrance box, and that the unit must be grounded before power is connected. It also covers matching supply voltage and phase to the converter, using an approved starter and switching device, and protecting the converter from unsuitable temperatures.
The manual then gives pre-installation guidance and wiring information. It explains 240V lead pairs (1&7, 2&8, 3&9), connecting leads 4, 5 and 6 together and insulating them, checking voltage balance by trying T1/T2/T3 combinations, and the expected voltages to ground on T1/T2 and T3. Wiring diagrams show single-phase input, three-phase output, optional isolation transformer and disconnect/starter arrangements, followed by installation steps and pictures.
| Converter supply voltage | 240 V operation |
|---|---|
| 240 V lead pairs | 1-7, 2-8, 3-9 |
| Leads 4, 5 and 6 | Connected together as one point and insulated |
| T1/T2 voltage to ground | Approximately 120 V |
| T3 voltage to ground | 190 to 210 V |
| Single-phase branch circuit rating | 2.5 times the three-phase current load |
| Maximum operating temperature | 40 °C |
Installation must be performed by a licensed electrician.
For 240 volt operation, the lead pairs are 1-7, 2-8 and 3-9.
T3 is a floating ground and should read between 190 and 210 volts to ground.
No. It must be connected to a separate electrical circuit directly from the entrance box.