This manual explains how to connect and operate the ALC Bacview service tool with ALC controllers for monitoring, status viewing, setpoint adjustment, and…
The Bacview service tool connects to ALC controllers via a service cable or hard‑wired 4‑pin plug, providing access to unit status, input states, limit switches, time delays, run‑time logs, and adjustable set points. The service cable uses color‑coded wires (red +12 V, blue Rnet‑, white Rnet+, black Gnd) that plug into the controller’s local access port; alternatively, the Bacview’s 4‑pin plug can be wired directly in parallel with an existing RSpro thermostat.
Once connected, the welcome screen shows the system program number and version. Navigation uses four soft‑touch keys below the display to move between status, set point, delay, and run‑time screens. Set points are edited by highlighting the desired line, pressing Enter, then using OK/Cancel/Decrease/Increase keys. For I/O Flex 6126 controllers, network settings (Arcnet and MS/TP numbers) can be cleared or set by holding Fn+9; advanced network information (BACnet device instance and base ID) is accessed with Fn+8.
| Connection method | Service cable (4‑pin) or hard‑wired 4‑pin plug |
|---|---|
| Service cable wiring | +12 V = Red, Rnet‑ = Blue, Rnet+ = White, Gnd = Black |
| Compatible controllers | ALC controllers (I/O Flex 6126, I/O Zone 583) |
| Set point editing | Highlight line, press Enter, use OK/Cancel/Decrease/Increase keys |
Use the arrow keys to move the quotes to the desired set point, press Enter to enter edit mode, then use the Decrease/Increase keys to adjust the value and press OK or Enter to save.
Hold Fn+9 to open the network screen, set the Arcnet network number to zero, then set the MS/TP network number to the desired value or to 1 to force a network search.