Product manual for the AK300-S2XF fire pump controller covering model description, system parameters, panel operation, wiring ports, dimensions and wiring…
This manual describes the AK300-S2XF fire electrical control device (fire pump controller), designed to comply with the GB16806-2006 standard for fire pump control equipment. It performs logic operations, automatic remote signal processing, contactor driving, voltage and current display, and load fault protection switching, and is suitable for pumps from 0.75 to 500 kW with direct, star-delta, soft start, or autotransformer reduced-voltage starting.
The document explains the model designation, system features such as customizable input/output ports, phase sequence and over/under-voltage protection, a password electronic lock, and LED display of line voltages, frequency, current and fault status. It also lists all system parameters with default values, describes the operating panel keys, display information and wiring ports, and provides product dimension drawings and wiring diagrams. This manual is written in Chinese.
| Working voltage | AC220V |
|---|---|
| Applicable pump power | 0.75–500 kW |
| Supported starting methods | Direct, star-delta, soft start, autotransformer reduced-voltage |
| Alarm sound level | >65 dB at 1 m |
| Status indicator visibility | Distinguishable color distance up to 6 m |
| Current rating setting range | 1–999 A |
| RS485 address range | 1–247 |
| RS485 baud rate | 2400 / 4800 / 9600 |
| Compliance standard | GB16806-2006 |
When the display shows locked, hold the Management Authority key for 3 seconds, enter the correct 3-digit password using the pump start/stop keys, then press the Management Authority key once to unlock.
In the unlocked state, hold the Auto/Manual and Main/Backup keys together for 5 seconds, enter password 777 and confirm with the Management Authority key to enter the function customization menu.
In parameter P11, long-press the Pump 1 Start or Pump 2 Start key; when YES is displayed, the factory configuration has been restored.
While pump 1 is running normally, press the Pump 1 Fault Switch key to simulate a pump 1 fault and automatically switch to pump 2; the Pump 2 Fault Switch key works the same way for pump 2.