ADD-Furnace VE3.2 Control Box User Manual

ADD-Furnace VE3.2 control box for forced draught gas burners up to 350 kW, with technical data, installation directions, and operating cycle.


ADD-Furnace VE3.2 Control Box User Manual - cover page
Brand
ADD FURNACE
Category
Other device
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
343 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0C9A6A50A316E30729AFB3E1B1D06BA9

About this manual

The VE3.2 control box is suitable for forced draught gas burners for civil and industrial applications, with power up to 350 kW and one flame level. It includes technical data, flame control information, construction details, dimensions, accessories, installation directions, thermal timers, and an operating cycle.

The document also describes reset after lockout, abnormal operation cases such as air flow failure and parasitic flame, and the electric scheme and connection options.

What's inside

  • DESCRIPTION
  • TECHNICAL DATA
  • FLAME CONTROL
  • CONSTRUCTION
  • OVERALL DIMENSIONS
  • ACCESSORIES
  • DIRECTIONS FOR INSTALLATION
  • THERMAL TIMERS
  • OPERATING CYCLE
  • RESET OF THE CONTROL

Specifications

Supply voltage220 V (-15% +10%), 50 Hz; 110 V on request
Operating temperature range-10 °C to +60 °C
Protection degreeIP40
Starting power consumption10 VA
Operating power consumption7 VA
Contact ratingFan motor 4 A; EV valve 2 A; ignition transformer 2 A; alarm 1 A; regulators 6 A
Prepurge time30 s
Safety time2 s
Drop-out time on running flame failure<1 s
Minimum ionization current0.5 µA
Recommended ionization current7 µA
Minimum insulation resistance of cable and detection probe to earth>50 MΩ
Voltage on detection probe300 V
Weight including socket585 g

Frequently asked questions

What is the minimum ionization current for flame control?

0.5 µA.

What is the prepurge time?

30 seconds.

How is the control reset after lockout?

Act on the reset button after waiting for restoration of the lockout thermal, usually about 20 seconds.

What happens if the flame extinguishes during normal running?

The gas flow is interrupted and a new cycle is started.

Download PDF (343 KB)

More ADD FURNACE Manuals