The DTC1000/2000 series of digital controllers are TD's C series controllers, which adopt isolated switch power supplies. They have PID programmable, manual or ON/OFF control modes, and can output relays, voltage pulses, currents or linear voltages. Support RS-485 digital communication
The Delta DTC series digital controllers (models DTC1000/1001 and DTC2000/2001) provide flexible temperature control with multiple input types, output options and RS‑485 Modbus communication. The manual details safety precautions, installation on DIN rails, wiring diagrams, and configuration of input sensors such as thermocouples and Pt100 RTDs.
Operational guidance includes PID, ON/OFF and manual control modes, programmable alarm functions (13 modes), password protection levels, and detailed register maps for setting communication parameters, output limits and program steps. Technical specifications, environmental limits and troubleshooting tips are also provided.
| Power supply | DC 24 V |
|---|---|
| Maximum relay load | 250 VAC, 3 A resistive |
| Communication interface | RS‑485, 2,400 bps – 38,400 bps |
| Communication protocol | Modbus (RTU/ASCII) |
| Operating temperature range | 0 °C – +50 °C |
| Storage temperature range | -20 °C – +65 °C |
| Operating humidity | 35 % – 85 % RH (no condensation) |
| Vibration resistance | 10 ~ 55 Hz, 10 m/s², 3‑axis |
| Shock resistance | Maximum 300 m/s², 3‑axis, 6‑direction |
| Supported input sensor types | Thermocouples K,J,T,E,N,R,S,B,L,U,TXK; Pt100, JPt100 RTDs |
| Alarm modes | 13 selectable modes |
It requires a 24 V DC isolated switching power supply.
The controller supports 2,400 bps up to 38,400 bps.
Thirteen different alarm output modes are available.
The unit must be installed in a dust‑, moisture‑ and shock‑protected enclosure with a lockable cabinet to prevent unauthorized access.