Morley alarm system installation manual, introduces the features, specifications and installation instructions of Morley alarm system.
The MorleyIAS Vision LT installation, configuration and operation manual, Doc. No-MIE-MI-580, covers VSN LT fire alarm control panels in 2, 4, 8 and 12 zone versions. It describes EN54 functions, the keypad and system indicators, installation and wiring for pushbuttons, sensors, sirens and alarm/fault relays, base board layout, programming options and technical specifications.
VSN LT panels include an integrated switched-mode power supply with battery charger and space for two sealed lead-acid batteries. Alarm zones can be configured as normal, confirmation-delay or verified zones, and the manual explains siren delays, auxiliary 24 V outputs and access levels. This manual is written in Spanish.
| Factory-configured zones | 2, 4, 8 or 12 zones |
|---|---|
| Maximum devices per zone | Up to 32 sensors (ECO1000 series) and/or alarm pushbuttons |
| Integrated power supply | 45 W (1.6 A) for Vision 2/4LT; 65 W (2.4 A) for Vision 8/12LT |
| Auxiliary 24 V output | 315 mA for VSN LT 2/4; 600 mA for VSN LT 8/12 |
| Maximum siren delay | 10 min |
| EN54 compliance | EN54 Parts 2 and 4 |
| Battery space | Two sealed lead-acid batteries |
The panels are factory-configured for 2, 4, 8 or 12 zones.
Each zone can accept up to 32 ECO1000 series sensors and/or alarm pushbuttons.
It supplies 315 mA on VSN LT 2/4 and 600 mA on VSN LT 8/12.
Enter access code 1221 while pressing the keypad key, using zone keys Z1, Z2, Z2 and Z1.