This paper briefly introduces the advantages of cone-shaped winding structure in the application of ultra-high voltage pulse transformer, and illustrates it through engineering practice.
This Chinese technical article from Hefei Huayao Electronic Industrial Co., Ltd. explains cone-shaped windings for ultra-high voltage pulse transformers. It describes how insulation thickness between primary and secondary windings varies linearly along the winding length while keeping the voltage gradient constant.
The article compares cone-shaped windings with conventional cylindrical windings, noting reduced leakage inductance and better economy. It also describes a developed transformer for a linear accelerator with 300 kV output voltage and a 20 kV primary winding. This manual is written in Chinese.
| Output voltage | 300 kV |
|---|---|
| Primary winding voltage | 20 kV |
It is a winding whose insulation thickness between primary and secondary varies linearly along the winding length while keeping the voltage gradient constant.
Leakage inductance is reduced by about one-half compared with ordinary windings.
The developed transformer was designed for 300 kV output voltage.