Hong Kong Oxygen & Acetylene Co. Ltd. User Manual and Safety Information for Industrial Liquid Gas Containers
This manual gives concise instructions for the safe installation, handling, storage, use, and maintenance of industrial liquid gas containers. It covers portable containers for liquid oxygen, liquid nitrogen, liquid argon, and liquid carbon dioxide, including safety precautions, personal protective equipment, first aid, and emergency procedures.
The document also explains container siting, storage compounds, ventilation, commissioning, connection and disconnection procedures, daily checks, pressure control, and maintenance. Appendices include a schematic diagram of a liquid gas container, an industrial liquid gas safety handling sheet, and references.
| Gases covered | Liquid oxygen, liquid nitrogen, liquid argon, liquid carbon dioxide |
|---|---|
| Liquid oxygen pressure | 230 psi |
| Liquid nitrogen pressure | 22/230/350 psi |
| Liquid argon pressure | 350 psi |
| Liquid carbon dioxide pressure | 350 psi |
| Container construction | Double wall construction with vacuum and multi layer insulation between two stainless steel vessels |
| Minimum separation distance | At least 5 metres from flammable gases and liquids, combustible materials, and public places when not stored in a two-hour fire-resistant store |
| Warm water bath temperature for first aid | Not exceeding 40 degrees centigrade |
| Clearance area after a container falls over or is dropped | 10 metres |
| Waiting time before raising a dropped container | Fifteen minutes |
They are defined as portable containers for the storage and delivery of liquid oxygen, liquid nitrogen, liquid argon, or liquid carbon dioxide.
Wear cold-resistant gloves, safety glasses or goggles, loose-fitting overalls without open pockets, and safety boots or shoes. A face shield should also be worn where spraying or splashing may occur.
Clear the surrounding area for 10 metres and wait fifteen minutes. If there is no frosting or other abnormal appearance, carefully raise the container to the vertical position and contact Hong Kong Oxygen for inspection.
Raise the alarm or call the fire brigade, evacuate people not fighting the fire, and spray water on the outer vessel from a safe distance to keep it cool. Hong Kong Oxygen must be advised if a container was affected by fire.