TE3301 series combined electrical fire monitoring detector is a detector for real-time monitoring of electrical fire. It can monitor residual current and temperature, and has sound and light alarm and relay output functions.
The TE3301 Series is a combined electrical fire monitoring detector designed to monitor residual current and temperature. It can analyze sensor signals, indicate normal, fault, and alarm states, and send real-time data over a bus to an electrical fire monitoring device for centralized display. It supports up to eight channels and automatic identification of connected temperature or residual-current sensors.
The manual covers technical parameters, terminal and panel descriptions, installation and wiring, and use and operation. It explains address and threshold settings, fault detection, and alarm detection, including indicator-light and key functions. The detector can be mounted on a DIN rail or embedded in a panel and is intended for use with the TE3004 electrical fire monitoring device. This manual is written in Chinese.
| Detection object | Residual current and temperature |
|---|---|
| Residual current detection range | 0 mA to 1000 mA |
| Temperature detection range | 0°C to 140°C |
| Communication method | Non-polar two-wire bus |
| Communication distance | ≤1000 m with NH-RVS 2×1.5 mm² cable; ≤600 m with NH-RVS 2×1.0 mm² cable |
| Operating voltage | AC 220 V/50 Hz or DC 24 V |
| Mounting method | DIN rail or panel embedded |
| Dimensions | 108.0 mm × 108.0 mm × 59.0 mm |
| Compatible monitoring device | TE3004 electrical fire monitoring device |
| Standards | GB 14287.2-2014 and GB 14287.3-2014 |
| Operating temperature | -10°C to +55°C |
| Relative humidity | ≤95%RH, non-condensing |
It supports up to 8 channels at the same time.
The address range is 1 to 200, and the default address is 1.
The temperature threshold defaults to 75°C, and the current threshold defaults to 300 mA.
Within 100 seconds, it reports the fault type and the affected channel and turns on the fault indicator.