Tanda TE3301 Series Combined Electrical Fire Monitoring Detector Installation and Operation Manual

TE3301 series combined electrical fire monitoring detector is a detector for real-time monitoring of electrical fire. It can monitor residual current and temperature, and has sound and light alarm and relay output functions.


Tanda TE3301 Series Combined Electrical Fire Monitoring Detector Installation and Operation Manual - cover page
Brand
Tanda
Category
Monitoring Equipment
Document type
User Manual
Language
Chinese
Pages
14
File format
PDF
File size
1.1 MB
Published
25 November, 2023
Updated
25 November, 2023
MD5 checksum
E1F682C57D37762D30012C2B674702D1

About this manual

The TE3301 Series is a combined electrical fire monitoring detector designed to monitor residual current and temperature. It can analyze sensor signals, indicate normal, fault, and alarm states, and send real-time data over a bus to an electrical fire monitoring device for centralized display. It supports up to eight channels and automatic identification of connected temperature or residual-current sensors.

The manual covers technical parameters, terminal and panel descriptions, installation and wiring, and use and operation. It explains address and threshold settings, fault detection, and alarm detection, including indicator-light and key functions. The detector can be mounted on a DIN rail or embedded in a panel and is intended for use with the TE3004 electrical fire monitoring device. This manual is written in Chinese.

What's inside

  • Overview
  • Features
  • Technical parameters
  • Structure and working principle
  • External terminals
  • Panel and indicators
  • Installation and wiring
  • Use and operation
  • Fault detection
  • Alarm detection

Specifications

Detection objectResidual current and temperature
Residual current detection range0 mA to 1000 mA
Temperature detection range0°C to 140°C
Communication methodNon-polar two-wire bus
Communication distance≤1000 m with NH-RVS 2×1.5 mm² cable; ≤600 m with NH-RVS 2×1.0 mm² cable
Operating voltageAC 220 V/50 Hz or DC 24 V
Mounting methodDIN rail or panel embedded
Dimensions108.0 mm × 108.0 mm × 59.0 mm
Compatible monitoring deviceTE3004 electrical fire monitoring device
StandardsGB 14287.2-2014 and GB 14287.3-2014
Operating temperature-10°C to +55°C
Relative humidity≤95%RH, non-condensing

Frequently asked questions

How many channels can the TE3301 series monitor at the same time?

It supports up to 8 channels at the same time.

What is the default address of the detector?

The address range is 1 to 200, and the default address is 1.

What are the default current and temperature thresholds?

The temperature threshold defaults to 75°C, and the current threshold defaults to 300 mA.

How quickly does the detector report a channel fault?

Within 100 seconds, it reports the fault type and the affected channel and turns on the fault indicator.

Download PDF (1.1 MB)