EMCO EE-302 Microcontroller-Based Automatic Voltage Regulating Relay Instruction Manual

EMCO's Microcontroller based Automatic Voltage Regulating Relay type EE-302 is a new generation Relay used for regulating the secondary voltage of Power Transformers with a motor driven On Load Tap Changer (OLTC).


EMCO EE-302 Microcontroller-Based Automatic Voltage Regulating Relay Instruction Manual - cover page
Brand
Emco
Category
Other Electronics
Document type
User Manual
Language
English
Pages
25
File format
PDF
File size
517 KB
Published
24 November, 2023
Updated
24 November, 2023
MD5 checksum
25EFEABEBB163A9E87EDBAF5A7238B7C

About this manual

The EMCO EE-302 is a microcontroller-based automatic voltage regulating relay designed to regulate the secondary voltage of power transformers equipped with motor-driven on-load tap changers (OLTC). It operates using programmable parameters stored in non-volatile memory, allowing for precise control of voltage deviation through raise or lower control pulses. The device features a membrane keyboard for setting parameters such as nominal voltage, time delays, and voltage limits, with results displayed on a 4-digit 7-segment LED display.

What's inside

  • General Description
  • Specifications
  • Indications / Controls / Inputs and Outputs
  • Operating Instructions
  • Typical Inspection Procedure
  • Functional Description of PCBs
  • Options
  • Fault Finding Procedure

Specifications

Nominal Voltage Setting Range85 to 140V
Lower Voltage Setting Range+0.5 to +9% of NS
Raise Voltage Setting Range-0.5 to -9% of NS
Time Delay T1 Range10 to 180 secs
Time Delay T2 Range0 to 11 secs
Undervoltage Blocking Range60 to 95% of NS
Overvoltage Detection Range105 to 130% of NS
Primary Voltage Factor Range0 – 999.9 KV
Contact Rating5A @ 240V AC or 24V DC
Operating Temperature0 – 45 0 C

Frequently asked questions

What is the function of the Control Fail Relay?

The Control Fail Relay signals when the voltage remains outside the deadband for more than 5 minutes.

How does the relay handle overvoltage conditions?

An overvoltage condition results in high speed return, initiating lower commands with 2 secs ON/OFF pulse duration.

Can the relay operate in manual mode?

Yes, the Auto / Manual selection allows the Relay to operate in Manual mode, where Raise and Lower pulses are blocked.

What are the steps for load shedding?

Load dependent voltage drops can be compensated by increasing or decreasing the desired value via loadshedding in 3 steps: 3%, 6%, and 9% of Nominal voltage.