Elektro-Mechanik FLA3.1L Fault Indicator and HS Remote Control Instruction Manual

The instruction manual for ELEKTRO-MECHANIK fault indicator type FLA3.1L and remote control type HS.


Elektro-Mechanik FLA3.1L Fault Indicator and HS Remote Control Instruction Manual - cover page
Brand
Elektro-Mechanik
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
15
File format
PDF
File size
2.1 MB
Published
24 November, 2023
Updated
24 November, 2023
MD5 checksum
F542749BB5A8BF493A6F405CFA8B293A

About this manual

The Elektro-Mechanik FLA3.1L is a fault indicator designed for radial overhead line networks. It continuously surveys the network for permanent faults, temporary faults, and transient currents. The device can be fully adjusted while in operation using a remote control, allowing for versatile application in various settings.

What's inside

  • Introduction
  • Fault indicator type FLA3.1L
  • Remote control type HS
  • Communication between remote control and fault indicators
  • Fault detection and indication
  • Automatic mode
  • Remote indication
  • Voltage detection
  • Autorecloser settings
  • Fault localization

Specifications

Short-circuit trip current range20A to 800A (fixed) or 150% to 500% (automatic)
Earth-fault trip current dt range5A to 100A
Response delay range40ms to 300ms
Reset time range30min to 720min
Voltage detection range20% to 90% of operating voltage
Maximum number of IDs9
Wake-up check cycle20 seconds

Frequently asked questions

What is the function of the FLA3.1L fault indicator?

It is used in radial overhead line networks to survey the net continuously for permanent faults, temporary faults, and transient currents.

How does the FLA3.1L indicate a temporary fault?

When a temporary fault is detected, there is an additional flash of the green LED every two seconds (0.5Hz frequency).

What does a yellow LED flash once per second indicate?

It signals that the FLA3.1L is in radio-mode and will receive and respond to commands from the remote control.

What happens if the battery voltage is too low?

The device enters emergency mode where fault detection and radio-mode are disabled, indicated by two flashes per second.