The handbook gives all the instructions for the installation and use of the Maglink LX console.
This manual provides instructions for the installation and use of the Maglink LX console, a device designed for monitoring level gauges and tank alarms in fuel tanks and hazardous areas. The document covers general warnings, installation site requirements, and electrical connection procedures, emphasizing safety protocols for use in explosive environments.
| Supply Voltage | 100-240 V~, 50/60Hz |
|---|---|
| Consumption | 15 VA |
| Working Temperature | -10 °C ÷ +50 °C |
| Number of Probes | 32 |
| Number of ON-OFF sensors | 16 |
| Number of slave displays | 4 |
| Relay output | 20 |
| Bus management capacity | up to 32 probes |
No, the console is not explosion-proof and must not be installed in hazardous areas.
A 250V – 1A fuse must be used.
The probes require 12Vdc at 100mA for each output.