The AFC-1000/AFC-1000V Fire Alarm Installation Manual provides instructions on how to install and operate the AFC-1000/AFC-1000V fire alarm system.
This manual provides installation instructions for the AFC-1000 and AFC-1000V addressable fire alarm panels. It details the main supply circuit, battery charging circuit, and proper separation of high-voltage and low-voltage wiring to ensure safe operation. The document includes specific requirements for connecting the main AC power, rechargeable batteries, and various output circuits.
| AC Input Power Rating (120V) | Maximum of 5A |
|---|---|
| AC Input Power Rating (240V) | Maximum of 3A |
| Battery Charging Voltage | 27.3 VDC |
| Battery Circuit Protection | 7 amp poly switch |
| Maximum Battery Size | 55 AH |
| Minimum Standby Time | 24 hours and 5 minutes |
| NAC Circuit Rating | 3 amps at 24 VDC |
| SLC Maximum Devices | 127 devices |
| SLC Voltage Range | 22-24 VDC |
| SLC Maximum Line Resistance | 50 ohms |
The maximum battery charging circuit is 1.0 amp DC.
Up to 9 additional SLC loops are supported by adding loop expander modules.
The maximum wiring resistance is 100 ohms.
The SLC has a maximum loop capacitance of 0.5 micro-farads.