This document describes a fire alarm system, including a fire alarm control unit, manual fire alarm boxes, system smoke detectors, heat detectors, notification appliances, a remote annunciator, an addressable interface device, and a digital alarm communicator transmitter.
This document serves as a construction specification manual for the installation of fire-alarm systems at the Salt River Project. It outlines the scope of work, including fire-alarm control units, manual boxes, smoke and heat detectors, and notification appliances. The manual specifies that the system must be a non-coded addressable evacuation system designed to meet applicable codes such as IFC, IBC, IMC, and NEC.
The system is dedicated to fire-alarm service only for the remodel and new addition areas.
The alarm relay must have contacts rated for a minimum of 10 amp.
Pull stations must be located with a maximum distance of 200 feet between them.