The Altistart 48 is a programmable AC motor soft starter for three-phase asynchronous motors. It has multiple functions, including current limitation, torque control, speed control and braking.
This user manual covers the Altistart 48 soft start-soft stop unit, including installation steps, factory configuration, preliminary recommendations, technical specifications, usage recommendations, motor matching, dimensions, and installation precautions.
It also describes power and control terminals, wiring and RUN-STOP control, application diagrams, thermal protections, display and programming, menus, compatibility, maintenance, faults with causes and solutions, and configuration/settings memory tables. This manual is written in Spanish.
| Current limitation (ILt) | 400% of motor current In |
|---|---|
| Acceleration ramp (ACC) | 15 seconds |
| Initial torque at start (tq0) | 20% of nominal torque |
| Motor thermal protection (tHP) | Class 10 protection curve |
| Communication speed (tbr) | 19,200 bits per second |
| Communication format (FOr) | 8 bits, no parity, 1 stop bit |
| Stop mode (StY) | Free-wheel stop |
| Analog output (AO) | Motor current, 0-20 mA |
| By-pass relay (R2) | By-pass relay at end of start |
The factory default acceleration ramp (ACC) is 15 seconds.
The default current limitation (ILt) is 400% of the motor current In.
The default motor thermal protection (tHP) uses a class 10 protection curve.
The default communication speed (tbr) is 19,200 bits per second.