ETCR 8100B Transformer Core Grounding Current Tester is a product specially designed and manufactured for online testing of transformer core grounding current and leakage current in power systems.
The Shanghai Huyi ETCR 8100B transformer core grounding current tester is designed for on-site online testing of transformer core grounding current and leakage current in power systems. It consists of a host, current clamp, monitoring software, and communication cable.
The host uses a high-speed microprocessor and a 3.5-inch color touch LCD. It can display the measured current and waveform in real time, store 200 groups of data and waveforms, and transfer stored data to a computer through a USB interface. The clamp has an 80 mm x 80 mm opening and can measure without disconnecting the tested line. This manual is written in Chinese.
| Function | Transformer core grounding current test; AC leakage current and current online test |
|---|---|
| Power supply | DC 9 V alkaline dry batteries, LR6 1.5 V x 6 |
| Test method | Clamp CT |
| Clamp opening size | 80 mm x 80 mm; can clamp a phi 80 mm conductor or a 96 mm x 4 mm flat steel ground wire |
| Range | Current: AC 0.00 mA to 1000 A; frequency: 10 Hz to 1000 Hz |
| Resolution | AC 0.01 mA |
| Accuracy | +/-1.5% +/-3 dgt |
| Display | 3.5-inch color touch LCD, 320 dots x 240 dots |
| Operation | Intelligent touch and key control |
| Host dimensions | 198 mm x 100 mm x 45 mm |
| Current clamp dimensions | 194 mm x 145 mm x 40 mm |
| Weight | Host: 450 g (with battery); current clamp: 780 g |
| LCD size | Display area: 71 mm x 53 mm |
| Electric field interference | About 10 mA when an external 100 A field is 10 mm away |
| Sampling rate | 2 times/second |
| Data storage | 200 groups; data are not lost on power loss or battery replacement |
| Alarm threshold setting range | 00.00 A to 99.99 A |
| Line voltage | AC 600 V and below |
| Overflow display | "OL" symbol |
| Low battery | Low battery symbol at 7.2 V +/- 0.1 V; measurements remain accurate |
| Rated current | Maximum 180 mA |
| Lead length | Current clamp lead length: 2 m |
| Operating temperature and humidity | -10 C to 40 C; below 80% RH |
| Storage temperature and humidity | -10 C to 60 C; below 70% RH |
| Dielectric strength | AC 2 kV/rms (between screw and housing) |
| Safety compliance | IEC1010-1, IEC1010-2-032, pollution degree 2, CAT III 600 V, IEC61326 (EMC) |
The current range is AC 0.00 mA to 1000 A, with a frequency range of 10 Hz to 1000 Hz.
It can store 200 groups of data and waveforms, and stored data are not lost when power is lost or the battery is replaced.
Yes. The automatic power-off time can be set from 000 to 999 minutes, and 000 means the tester does not power off automatically.
The low battery symbol appears when battery voltage drops to 7.2 V +/- 0.1 V, and measurements remain accurate at that point.