The Crest Control System Intelligent Barrier User Manual introduces the installation, commissioning and maintenance of the Crest Control System Intelligent Barrier.
This document is the User Guide for the Crest Control System G-F621 series intelligent barriers. It covers safety precautions, construction preparation including wiring principles and cable laying, and the installation and debugging process for the specific G-F621 model. This manual is written in Chinese.
| Motor Rated Power | 120W |
|---|---|
| Operating Temperature | -20°C~50°C |
| Power Supply Voltage | 220VAC±10%/(47~60HZ) |
| Barrier Operation Time | 1.5 seconds |
| Relative Humidity | ≤95% |
| Communication Distance (RS485) | ≤1200 meters |
| Remote Control Distance | ≤30 meters |
| Input Interface | Low level signal or pulse >100mS |
The manual recommends using a cable of (RVV3×1.0mm²) for equipment power supply.
The minimum standard for the wired control button opening signal cable is 6-core RVVP0.5mm².
The vertical deviation of the barrier after installation should not exceed 3mm.
The grounding resistance must be less than 4Ω and the grounding line must be reliably grounded.