SIEMENS SY(2.9)U230-SR/MF-T actuator SY(2.5)U24-SR/MF/MP-T modulating actuator Circuit Board Set Up Wiring diagram
This document provides installation, wiring, and adjustment instructions for the SY(2...9)U230-SR/MF-T and SY(2...5)U24-SR/MF/MP-T modulating actuators. It covers mounting to a butterfly valve, wiring according to the diagram, manual operation, and checking DIP switch settings.
It also explains travel cam and limit switch adjustment, auxiliary switch settings, closed position setup, and mechanical rotation limits using stop screws. Power supply options shown are AC 24 V and AC 230 V.
| Power supply | AC 24 V or AC 230 V |
|---|---|
| Auxiliary switches | 75% duty cycle SPDT relays |
| Electrical travel | 90° |
| Manual rotation limit range | -2° to 92° |
| Auxiliary switch factory settings | Closed 3°, open 87° |
| Limit switch factory settings | Closed 0°, open 90° |
| Stop screw adjustment | Maximum ±2°, about 1 turn |
Wiring the power supply common/neutral and control signal "-" to a common is prohibited.
The auxiliary switch for closed is set to 3° and for open to 87°.
Stop screws 1 and 2 limit manual rotation, with a maximum of about ±2° per turn.
The wiring diagrams show AC 24 V and AC 230 V supplies.