This document is the installation, operation and maintenance instructions for the Newport oil-fired boiler.
This manual provides installation, operation and maintenance instructions for the Trianco Newport oil-fired boiler. It covers safety warnings, boiler location and clearances, combustion and ventilation air, chimney draft, oil and fuel piping, electrical wiring, controls, domestic water piping, cleaning, burner service and tankless coil maintenance.
The document is published by LAARS Heating Systems and includes figures, component locations, dimensions and part numbers. It is intended for qualified installers and service technicians.
| Clearance to combustibles - top | 6 in (152 mm) |
|---|---|
| Clearance to combustibles - front | 24 in (610 mm) |
| Clearance to combustibles - rear | 6 in (152 mm) |
| Clearance to combustibles - sides | 6 in (152 mm) |
| Minimum smoke pipe connector length | 18 in (457 mm) |
| Combustion and ventilation air | 1 sq in per 1,000 BTU/h input or 140 sq in per gallon of oil per hour |
| Chimney overfire draft | 0.01 in. W.C. |
| Fuel | No. 2 heating oil only |
| Fuel line - single pipe | Not less than 3/8 in OD copper tubing |
| Fuel line - two pipe | Not less than 3/8 in OD copper tubing |
| Domestic hot water tempering valve setting | 120°F mixed delivery temperature |
| Pressure relief valve maximum | 150 PSI |
| Aquastat relay | Honeywell L8124A |
| Low limit setting | Usually 190°F to 210°F |
| High limit setting | 20°F to 30°F above low limit |
Only No. 2 heating oil should be used; gasoline, crankcase drainings, or oil containing gasoline must not be used.
Top 6 inches, front 24 inches, rear 6 inches, and sides 6 inches.
The boiler should be cleaned at least once a year, preferably at the end of the heating season.
The draft regulator should be adjusted to achieve an overfire draft of 0.01 in. W.C.