Quasar 900 Open-Path Gas Detection System User's and Maintenance Manual
The SafEye Quasar 900 Open-Path Gas Detection System is designed for the simultaneous detection of C1-C8 flammable gases. The system operates using a microprocessor-based flash source and detector unit, utilizing a spectral response of 2.0 - 3.0 microns to identify gas concentrations. It features a line-of-sight field of view with an alignment tolerance of ± 0.5° and includes heated optics to prevent condensation.
| Detected Gases | Simultaneous detection of C1-C8 flammable gases |
|---|---|
| Response Time | 3 sec to T90 |
| Spectral Response | 2.0 - 3.0 micron |
| Operating Voltage | 18-32 VDC |
| Water and Dust Tight | IP66 and IP68 |
| Temperature Range | -67°F (-55°C) to +149°F (+65°C) |
The maximum detection distance ranges from 23 ft (7 m) for the 901 model up to 660 ft (200 m) for the 904 model.
Yes, it is certified as ATEX & IECEx EX II 2 GD, Ex d e ib [ib Gb] IIB+H2 T4 Gb Ex tb IIIC T135°C Db.