TECSYSTEM NT935 IR Temperature Controller Instruction Manual

The NT935 IR is a multifunctional temperature controller with the following features: - Microprocessor control for high precision and stability. - Multiple input/output interfaces for connecting various sensors and actuators. - Multiple control modes to meet the needs of different users. - Multiple alarm functions to ensure the safe and reliable operation of the system.


TECSYSTEM NT935 IR Temperature Controller Instruction Manual - cover page
Brand
TECSYSTEM
Category
Monitoring Equipment
Document type
User Manual
Language
English
Pages
33
File format
PDF
File size
1.5 MB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
A7F4F93A73A9432A7A5F8FCBB3AF27A1

About this manual

This manual applies to the NT935 IR BASIC and NT935 IR AD control units. It covers safety requirements, supplied accessories, technical specifications, front-panel controls and displays, assembly, and electrical connections.

It also describes programming, RS485 Modbus communication for the AD version, fail-safe function, FCD function, troubleshooting, warranty conditions, equipment disposal, and useful contacts.

What's inside

  • Safety requirements
  • Accessories
  • Technical specifications
  • Front panel
  • Assembly
  • Electrical connections
  • Programming
  • RS485 Modbus
  • Fail safe function
  • Troubleshooting

Specifications

Power supply (rated)24-240 Vac-Vcc, 50/60 Hz
Power supply (minimum/maximum)20-270 Vac-Vcc, 50/60 Hz
Maximum consumption7.5 VA
Ambient operating temperature-20°C to +60°C
Humidity90% non-condensing
Frontal protectionIP65
IR sensor reading range-40°C to +200°C
Measurement angle10° (FOV)
4-20 mA interface accuracy±0.5% vfs, ±1 digit
Output relay rating10 A, 250 Vac, cosφ=1
Temperature alarm setting0°C to 200°C
Inputs4 inputs, 4-20 mA (-40°C at 4 mA, +200°C at 20 mA)

Frequently asked questions

What power supply does the NT935 IR accept?

It has a universal power supply rated 24-240 Vac-Vcc at 50/60 Hz, with minimum and maximum values of 20-270 Vac-Vcc.

What is the ambient operating temperature range?

The ambient operating temperature range is from -20°C to +60°C.

Which version supports RS485 Modbus?

RS485 Modbus is provided only for the NT935 IR AD version.

How should the control unit be cleaned?

Disconnect the power cable and clean the unit with a dry cloth without solvents or detergents, using compressed air.