This product is a multi-function energy analyzer with the following features: 1. High measurement accuracy, up to 0.5 level; 2. Wide measurement range, can measure voltage, current, power, energy and other parameters; 3. Powerful functions, with data recording, alarm, communication and other functions; 4. Simple operation, convenient for users to use.
This manual provides instructions for the POWYS 1xxx series energy analyzer, a device designed for single-phase systems to measure voltage, current, frequency, power, and harmonics. It details the general features, safety conditions, and connection types for various models including the POWYS 1110, 1120, 1012, 1022, and 1023.
| Supply Voltage | 85..300 V AC/DC |
|---|---|
| Operating Temperature | -20°C..+70°C |
| Power Consumption | < 2W |
| Measurement Input Voltage | 10..500V AC |
| Measurement Input Current | 10mA .. 6A AC |
| RS485 Baudrate | 1200 - 57600 |
It measures voltage, current, network frequency, CosØ value, power factor, active power, reactive power, apparent power, THDV, THDI, and voltage/current harmonics.
The CTR setting may be entered from 1 to 5000, and the VTR setting may be entered from 0.1 to 5000.
The POWYS 1110 and POWYS 1120 models feature LCD displays, while others use 7-segment displays or LEDs.