This series of products are combined residual current circuit breakers/miniature circuit breakers with a rated working voltage of 230/400V, a rated frequency of 50Hz, a residual operating current of 0.03A to 0.3A, a rated current of 6A to 20A, and a short-circuit breaking capacity of 10kA.
This document is a technical data sheet for the TECONEX FL9 series of 2-pole Combined RCD/MCB Devices. It details the device's electrical design, rated values, and physical dimensions according to IEC/EN 61009 standards. Key features include line voltage-independent tripping, compatibility with standard busbars, and a twin-purpose terminal design.
| Rated voltage Ue | 230 V AC; 50 Hz |
|---|---|
| Operational voltage range | 196-253 V |
| Rated tripping current IΔn | 30 - 100 - 300mA |
| Sensitivity | AC and pulsating DC |
| Rated breaking capacity Icn | 10 kA |
| Rated current | 6 - 10 - 16 - 20 A |
| Characteristic | C |
| Maximum back-up fuse | 100 A gL (>10 kA) |
| Device height | 80 mm |
| Device width | 35 mm (2MU) |
| Degree of protection, switch | IP20 |
| Degree of protection, built-in | IP40 |
| Terminal capacity | 1 - 25 mm² |
| Terminal torque | 2 - 2.4 Nm |
| Tripping temperature | -25°C to +40°C |
| Storage and transport temperature | -35°C to +60°C |
The test key 'T' must be pressed every 6 months for residential and similar applications.
No, pressing the test key only tests the residual current device function and does not replace earth resistance measurement.
The rated breaking capacity is 10 kA.