TECONEX FL9 Combined RCD/MCB Devices Technical Data Sheet

This series of products are combined residual current circuit breakers/miniature circuit breakers with a rated working voltage of 230/400V, a rated frequency of 50Hz, a residual operating current of 0.03A to 0.3A, a rated current of 6A to 20A, and a short-circuit breaking capacity of 10kA.


TECONEX FL9 Combined RCD/MCB Devices Technical Data Sheet - cover page
Brand
TECONEX
Category
Other Electronics
Document type
Datasheet
Language
English
Pages
5
File format
PDF
File size
1.1 MB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
1DEFEF552FD062834699941E4BE84C9C

About this manual

This document is a technical data sheet for the TECONEX FL9 series of 2-pole Combined RCD/MCB Devices. It details the device's electrical design, rated values, and physical dimensions according to IEC/EN 61009 standards. Key features include line voltage-independent tripping, compatibility with standard busbars, and a twin-purpose terminal design.

What's inside

  • Technical Data
  • Influence of Ambient Temperature
  • Connection Diagram
  • Dimensions
  • Electrical Design
  • Tripping Characteristic
  • Short Circuit Selectivity
  • Let-through Energy

Specifications

Rated voltage Ue230 V AC; 50 Hz
Operational voltage range196-253 V
Rated tripping current IΔn30 - 100 - 300mA
SensitivityAC and pulsating DC
Rated breaking capacity Icn10 kA
Rated current6 - 10 - 16 - 20 A
CharacteristicC
Maximum back-up fuse100 A gL (>10 kA)
Device height80 mm
Device width35 mm (2MU)
Degree of protection, switchIP20
Degree of protection, built-inIP40
Terminal capacity1 - 25 mm²
Terminal torque2 - 2.4 Nm
Tripping temperature-25°C to +40°C
Storage and transport temperature-35°C to +60°C

Frequently asked questions

How often must the test key be pressed?

The test key 'T' must be pressed every 6 months for residential and similar applications.

Does the test key check earthing resistance?

No, pressing the test key only tests the residual current device function and does not replace earth resistance measurement.

What is the rated breaking capacity?

The rated breaking capacity is 10 kA.