The PET1000N electronic CT calibrator has the characteristics of high precision, wide range, full function and simple operation.
The PET1000N electronic current transformer calibrator from Ponovo can verify ratio errors for digital-output, analog-output and conventional electromagnetic current/voltage transformers, and performs automatic data processing. It also provides small-signal harmonic output and FT3 output functions for testing merging units.
The instrument uses high-precision 16-bit A/D conversion and digital signal processing, with a stated accuracy class of 0.05. It supports IEC 61850-9-1, IEC 61850-9-2LE, standard FT3, extended FT3 and Nanrui FT3 protocols, along with PPS and IRIG-B clock synchronization methods. This manual is written in Chinese.
| Standard voltage transformer input range | AC 0-120 V (RMS) |
|---|---|
| Measured voltage transformer input range | AC 0-120 V (RMS) |
| Standard current transformer input range | AC 0-6 A (RMS) |
| Measured current transformer input range | AC 0-6 A (RMS) |
| Analog small-signal input range | AC 0-7 V (RMS) |
| Analog small-signal output range | AC 0-7 V (RMS) |
| Current measurement accuracy | 0.05% for AC 0.1-6 A |
| Voltage measurement accuracy | 0.05% for AC 10-120 V |
| IEC 61850-9-1 rated voltage parameter | 11585 (0x2D41) |
| IEC 61850-9-2 digital voltage unit | 10 mV |
| IEC 61850-9-1 rated protection current parameter | 463 (0x1CF) |
| IEC 61850-9-1 rated measurement current parameter | 11585 (0x2D41) |
| IEC 61850-9-2 digital current unit | 1 mA |
| Communication interface | 100 M Ethernet port |
| FT3 fiber type | Multimode fiber, 62.5/125 um |
| Synchronization signal optical wavelength | 1310 nm |
| Insulation resistance, power input to ground | >300 MΩ with 1000 V megohmmeter |
| Power supply | AC 220 V, 50 Hz, 5 A |
| Accuracy class | 0.05 class |
It requires an AC 220 V, 50 Hz, 5 A power supply.
The companion software is recommended to run on Windows XP or Windows 7.
It is recommended to warm up the instrument for more than 10 minutes after power-on.
The calibrator achieves accuracy class 0.05.