The GSCM-mini is a micro-processor based generator start-stop module, designed to auto start-stop high speed gas generators needing a 3 wire connection from a 2 wire manual start command. It automatically disconnects the starter when a minimum generator AC Hz. output is measured. It can monitor the generator’s output for an over or under Hz condition and shut it down if either is detected. The Gen. Hz LED is blinks to indicate the cause of the shutdown. Manually resetting the GSCM-mini by removing the power, removes any fault shutdown and allows the generator to restart if called to do so. The GSCM-mini is powered by 12VDC from the generator battery, and can monitor the battery voltage and start the generator to charge it’s own battery. All Thresholds are fixed. The GSCM-mini is a limited function controller, limited to starting and stopping the generator.
The GSCM-MINI-50HZ from Atkinson Electronics is a microprocessor-based generator start-stop module that lets a 2-wire manual start command control a high-speed gas generator with a 3-wire connection. It monitors generator AC Hz and battery voltage and can shut down the generator on over- or under-frequency faults.
The document covers three relay configurations (momentary, maintained, ignition), six LED indicators, fixed operational thresholds, and wiring and starting sequences for each configuration.
| Crank delay | 5 seconds |
|---|---|
| Maximum crank time | 20 seconds |
| Crank disconnect frequency | 35 Hz |
| Under-speed shutdown | 45 Hz |
| Over-speed shutdown | 55 Hz |
| Maximum auto-start run time | 6 hours |
| 12 V system auto start/stop thresholds | Start 11.5 V; stop 13.8 V |
| 24 V system auto start/stop thresholds | Start 23.0 V; stop 27.6 V |
| 48 V system auto start/stop thresholds | Start 46.0 V; stop 55.2 V |
| Power source | 12 VDC from generator battery |
| Start failure fault detection | 3 attempts |
| Over Hz fault detection | 10 seconds |
The GSCM-mini supports momentary, maintained, and ignition key-switch start/stop configurations.
The maximum auto start run time is 6 hours.
It is powered by 12 VDC from the generator battery.
Remove power from terminal 2 and reconnect it to clear the lockout.