NRG Systems 1kW Propane Autonomous Power Unit Kit Instruction Manual. The generator has been modified to operate on propane or natural gas and to allow for extended, continuous operation beyond the original manufacturer’s specifications.
This instruction document from NRG Systems (Rev 5, 9 January 2012) covers the 1kW Propane Autonomous Power Unit Kit, a retrofit applied to a Yamaha EF1000iS generator converted to run on propane or natural gas by US Carburetion. It explains the engine crankcase auto oiler system, in which the generator fuel tank is used only as an oil reservoir feeding the crankcase by gravity through a controlled valve, with an electronics module monitoring oil level and shutting the generator down on a low oil situation.
The document gives warnings, oil and propane requirements for extended runtime, a fuel consumption table for 40-day operation, maintenance items, retrofit and installation recommendations, and step-by-step assembly and starting instructions including priming, load block adjustment and checking or changing the oil. Propane/natural gas operation and troubleshooting are referred to the US Carburetion Master Guide and general generator maintenance to the Yamaha EF1000iS Owner's Manual.
| Stock generator oil capacity (Yamaha EF1000iS) | 0.34 US quarts (0.32 liters) |
|---|---|
| Oil reservoir capacity | 2.64 US quarts (2.5 liters) |
| Required oil | Mobil 1, 5W-30 Synthetic Oil |
| Autonomous continuous runtime | 40 days |
| Propane use at 25% load | 1.40 gallons / 5.3 liters per day (56 gallons / 212 liters for 40 days) |
| Propane use at 100% load | 3.70 gallons / 14 liters per day (148 gallons / 560 liters for 40 days) |
| Electrical load at 100% | 900 Watts |
| Crankcase fill quantity for oil change | 320 mL of fully synthetic 5w-30 oil |
| Warranty period | 1500 hours of operation |
The retrofit allows the EF1000iS to operate for 40 continuous days autonomously, using the automatic oil feed system.
Mobil 1, 5W-30 Synthetic Oil is required, and the oil reservoir should be filled before every extended operation deployment.
No. The fuel tank is used only as an oil reservoir and is not a fuel tank; never add gasoline to it.
Close the propane tank valve so that all fuel in the generator and fuel hose has been consumed.