Nassar Electronics EN-3 Electronic Water Level Controller User Manual

The EN-3 electronic water level controller is a device that automatically starts or stops a water pump depending on the water level. The unit is easy to install, operate and maintain.


Nassar Electronics EN-3 Electronic Water Level Controller User Manual - cover page
Brand
Nassar Electronics
Category
Other Electronics
Document type
User Manual
Language
Spanish
Pages
5
File format
PDF
File size
936 KB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
BECF325E8EFA788FE289B19CB6B38760

About this manual

The EN-3 is an electronic water level controller from Nassar Electronics (Monterrey, Mexico) that starts and stops a pump using three electrodes: common EC, low EB and high EA. It operates from 120 or 220 VAC and provides a relay contact (C, NA, NC) for direct pump operation or for connection to a starter coil. The manual lists installation warnings, wiring of the supply to terminals T1, T2 and T3, the function of the LINE, PUMP, EB and EA indicator LEDs, and the jumper between VA and EC that selects drain control instead of fill control.

The guide also explains how to prepare and install the electrodes, including the recommended distances and the plastic pipe or hose mounting used to protect submersible pumps against low suction level, plus a four-step test procedure to check the unit and the wiring. A specification table, warranty terms of 3 years from the date of purchase and a limitation of liability close the document. This manual is written in Spanish.

What's inside

  • Advertencias importantes
  • Alimentación de voltaje
  • LEDS indicadores
  • Control de vaciado
  • Control de llenado
  • Protección por bajo nivel de succión
  • Preparación de electrodos
  • Recomendaciones para instalar los electrodos dentro de un tubo o manguera de plástico
  • Prueba de funcionamiento
  • Especificaciones

Specifications

Supply120/220 VAC ± 10%, 50/60 Hz
Electrode voltage18 VAC
Electrode currentMax. 0.36 mA AC
Liquid resistanceMax. 50 kohms
Electrode cable lengthMax. 300 m (5000 m on request)
Maximum consumption3 W
Contact capacityNA 12 A, NC 8 A
Direct capacity1.5 HP max. at 220 V, 3/4 HP max. at 120 V
Contact life10,000,000 max., 200,000 at full load
Weight392 g
EnclosureABS

Frequently asked questions

How is the EN-3 set for drain (emptying) control?

Place a jumper between terminals VA and EC; for fill control no jumper is used between VA and EC.

How do I test the EN-3?

Feed 120 VAC to terminals T1 and T2 and jumper VA to EC; the green LINE LED should light, then jumper EC to EB and EC to EA to check the EB and EA LEDs and the pump contact.

What cable can be used to wire the electrodes?

Cable from gauge 12 to 18 may be used, preferably in three different colors to avoid connection errors.

How long is the warranty?

The product is covered against manufacturing and component defects for 3 years from the date of purchase.

Download PDF (936 KB)