About this manual

The Grässlin operating manual covers the taxxo E 45-1-MID digital and taxxo M 45-1 analog energy meters, which record the active energy of a single-phase AC circuit. It begins with safety information warning of the risk to life from electric shock and stating that only a trained electrician may perform installation and assembly.

The document then describes proper use (DIN rail mounting, dry rooms only, away from devices with inductive discharge), lists the technical data for both models, explains the flashing LED consumption display, and gives the DIN-rail assembly steps together with the connection diagram and its terminal assignments. The text is printed in several languages, with German and English first. This manual is written in German.

What's inside

  • Safety information
  • Device description
  • Proper use
  • Technical data
  • Consumption display
  • Installation and assembly
  • Assembly on DIN rails
  • Connection diagram (FIG. 1)

Specifications

Dimensions H x W x D120 x 18 x 63 mm (taxxo E 45-1-MID); 118 x 18 x 63 mm (taxxo M 45-1)
Number of phases1
DisplayLCD 5+2 = 99999.99 kWh (taxxo E 45-1-MID); 5+1 = 99999.9 kWh (taxxo M 45-1)
Mains voltage230 V AC, ±20%
Base current (Ib)5 A
Limit current (Imax)45 A
Connection modedirect
Starting current0.004 Ib
Frequency50 Hz
Own power consumption≤ 0.4 W / ≤ 8 VA
Pulse output1000 pulses/kWh; 12-27 VDC, ≤ 27 mA, max. cable length 20 m
Pulse length80 ms (taxxo E 45-1-MID); 90 ms (taxxo M 45-1)
Ambient temperature-25°C to +55°C
Accuracy classB (taxxo E 45-1 MID); 1 (taxxo M 45-1)
Degree of protectionIP51
Protection classII
Max. conductor cross-section12 mm2

Frequently asked questions

What is the difference between the taxxo E 45-1-MID and the taxxo M 45-1?

The taxxo E 45-1-MID is the digital version with an LCD display of 5+2 = 99999.99 kWh, while the taxxo M 45-1 is the analog version with a 5+1 = 99999.9 kWh display.

Who is allowed to install and connect the meter?

Only a trained electrician may perform installation and assembly. The power supply must be switched off and secured against being switched on again.

What does the flashing LED on the front show?

It indicates the measured energy flow, flashing 1000 times per kilowatt-hour.

Where can the energy meter be mounted?

It is assembled only on DIN rails and is suitable for use in dry areas only.