The GC-3822 module is an I/O module that integrates 2 temperature sensor (PT100) input channels. The module can be used to collect temperature information in real time and send the collected values to the GCAN-PLC-400/510/511 series controller or GCAN-8000/8100/8200/8300 series coupler via the internal bus.
This is the Chinese user manual (document version V3.13, 2022/11/16) for the GC-3822, an I/O module from Shenyang Guangcheng Technology (GCAN) that integrates two PT100 temperature sensor input channels. The module collects temperature values in real time and sends them over the internal bus to GCAN-PLC-400/510/511 controllers or GCAN-8000/8100/8200/8300 couplers, and it can be combined with other GC series I/O modules.
The manual describes the module's functions and features, mounting on the DIN rail next to a fieldbus coupler, the screw-terminal wiring method with the terminal assignments, and the meaning of the red ERROR and green RUN indicators. It also gives example address definitions for ST programming with GCAN-PLC controllers, an example CAN data frame for GCAN-IO-8000 series devices, the GC series I/O module selection table, and the technical specifications. This manual is written in Chinese.
| Input points | 2 |
|---|---|
| Wiring | 3-wire |
| Sensor type | PT100 |
| Temperature range | -200 to +500 °C |
| Resolution | 0.1 °C per digit |
| Conversion time | less than 250 ms |
| Electrical isolation | 500 Vrms |
| Current consumption | about 200 mA |
| Operating temperature | -40 °C to +85 °C |
| Dimensions | 100 mm x 69 mm x 12 mm |
| Protection class | IP 20 |
The module contains 2 input groups and can connect up to 2 PT100 sensors, wired in 3-wire form.
It is powered through the GCAN-PLC-400/510/511 controller or GCAN-8000/8100/8200/8300 coupler, so no separate power supply is needed.
The green RUN light stays on when the PT100 is connected correctly, and the red ERROR light stays on when no temperature sensor is connected.
The stated measurement range is -200 to +500 °C.