The LH500 transformer new neutral point assembly is used for the 110kV coil neutral point of power transformers. It is composed of single-phase isolating switches, neutral point lightning arresters, disconnectors, current transformers and discharge gaps. It is used to realize the transformer 110kV coil neutral point grounding or It has two different operating modes of non-grounding, and clamps the neutral point power frequency overvoltage, while preventing the misoperation of the relay protection caused by the discharge of the rod gap under lightning and operation overvoltage.
The LH500 is a new-type neutral point assembly device made by Shaanxi Lanhe Electric Engineering Co., Ltd. It is dedicated to the neutral point of 110 kV power transformer windings and is composed of a single-phase disconnector, neutral point arrester, decoupler, current transformer, and discharge gap. It allows the transformer neutral point to operate either grounded or ungrounded, clamps power-frequency overvoltage at the neutral point, and prevents relay protection misoperation caused by rod gap discharge under lightning and switching overvoltage.
The device integrates the disconnector, metal-oxide arrester, discharge gap, and current transformer in a compact assembly. It is small in size, easy to install and commission, and highly reliable, suitable for both new projects and retrofit optimization of existing arresters. This brief manual covers its purpose, working principle, structural features, model code, operating environment conditions, and technical parameters. This manual is written in Chinese.
| Transformer rated voltage | 110 kV |
|---|---|
| Neutral point lightning full-wave and chopped-wave withstand voltage | 250 kV (peak) |
| Neutral point 1-min power-frequency withstand voltage | 95 kV (RMS) |
| Disconnector operating mechanism | CS14G or CJ2 |
| Metal-oxide arrester rated voltage | 42 kV (RMS) |
| Arrester DC 1 mA reference voltage | not less than 65 kV |
| Arrester lightning impulse current residual voltage | not more than 120 kV |
| Discharge gap electrode distance range | 90-115 mm |
| Discharge gap power-frequency discharge voltage range | 50-65 kV (RMS) |
| Current transformer type | Epoxy resin cast fully enclosed post type, 10 kV |
| Current transformer ratio | 200/5, 300/5, 400/5 |
| Altitude | not more than 2000 m |
| Ambient temperature | -50°C to +50°C |
| Wind speed | not more than 34 m/s |
It is dedicated to the neutral point of 110 kV power transformer windings, providing grounded or ungrounded operation while clamping power-frequency overvoltage and preventing relay protection misoperation caused by rod gap discharge.
It consists of a single-phase disconnector, neutral point arrester, decoupler, current transformer, and discharge gap.
It is suitable for installation sites at altitudes not exceeding 2000 m.