Design Specification for Substations of 20kV and Below

This standard applies to the design of new, expanded and reconstructed substations for AC voltage up to and including 20kV.


Design Specification for Substations of 20kV and Below - cover page
Category
Other
Document type
Other
Language
Chinese
Pages
14
File format
PDF
File size
422 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
9D8489DB34E0FED995833802351B76F7

About this manual

This document is the national standard GB 50053-2013, titled "Design Specification for Substations of 20kV and Below". It provides guidelines for the design of new, expanded, and reconstructed substations to ensure safety, reliability, and economic efficiency.

The specification covers critical aspects including site selection criteria, electrical arrangements such as busbar connections and transformer configurations, and requirements for auxiliary power sources. It also details layout requirements for distribution devices and specific provisions for parallel capacitor installations. This manual is written in Chinese.

What's inside

  • General Provisions
  • Site Selection
  • Electrical Parts
  • Main Busbar Connections
  • Transformers
  • Auxiliary Power
  • Layout of Distribution Devices
  • Parallel Capacitor Installations
  • Fire Protection Requirements
  • Building and Ventilation Requirements

Frequently asked questions

What voltage range does this design specification apply to?

It applies to AC voltage of 20kV and below for new, expansion, and renovation substation design projects.

What is the recommended maximum capacity for a single transformer with 0.4kV low voltage?

The capacity should not exceed 1250kVA.

What connection group should distribution transformers in low voltage networks use?

They should use D,yn11 connection group three-phase transformers.