Segurimax Addressable Temperature and Smoke Detectors Manual

This product is a commonly used detector in fire alarm systems, it can detect the heat and smoke generated in the early stages of a fire and send out an alarm signal.


Segurimax Addressable Temperature and Smoke Detectors Manual - cover page
Brand
Segurimax
Category
detectors
Document type
User Manual
Language
Portuguese
Pages
2
File format
PDF
File size
632 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
D0F8DB1E10BDE3993C4C210FFCE4F558

About this manual

This Portuguese-language manual covers Segurimax addressable temperature and smoke detectors designed for fire detection and alarm systems in commercial and residential buildings, industries, hospitals, schools and recreation areas. The temperature detector is a thermovelocimetric device for environments where combustion produces much heat and little smoke, while the smoke detector uses an optical chamber with an insect and dust protection mesh and automatic contamination compensation.

The manual includes precautions, installation steps for mounting the detector base and connecting the loop cables, addressing instructions (referring to the Segurimax addressable central manual), testing guidance per ABNT NBR 17240-5 and 17240-7, a technical specification table and a one-year warranty term. This manual is written in Portuguese.

What's inside

  • Cuidados
  • Detector de Temperatura
  • Detector de Fumaça
  • Informações Técnicas
  • Endereçamento
  • Testes
  • Cuidados com a Instalação
  • Instalação
  • Termo de Garantia

Specifications

Operating voltage20 to 30 VDC
TopologyAddressable
SensitivityClass A2R 0.14 to 0.23 dB/m
Standby consumption≤0.4 mA
Alarm consumption≤2 mA
Installation2 loop wires, no polarity
Installation classClass A or B
Address range1 to 250
Operating temperature-10°C to 50°C
Humidity≤95% (non-condensing)
Protection ratingIP20 (indoor use)
Weight102 g (temperature) / 113 g (smoke)
DimensionsØ98 x 40 mm
MaterialABS plastic
Warranty1 year

Frequently asked questions

At what temperature does the Segurimax temperature detector trigger?

It is a thermovelocimetric detector that triggers with sudden temperature increases or when the limit of 57±3°C is exceeded.

How are the loop cables connected to the detector base?

Connect L+ to terminal 2 and L– to terminal 5 on the detector base.

Which standard should the installation project follow?

The installation project must be done by a professional with knowledge of ABNT NBR 17240 for fire detection and alarm systems.