The Weidmuller voltage monitoring module ACT20P- VMR- 3PH- I LP- H is a three-phase AC voltage relay with overvoltage, undervoltage, asymmetry, phase sequence and frequency monitoring functions, and has relay outputs and analog outputs.
This document is the Chinese user manual (使用说明书) for the Weidmüller ACT20P-VMR-3PH-ILP-H three-phase AC voltage monitoring and alarm relay, order number 7760054165. It monitors three-phase AC voltage signals with an input range of 180–500 VAC and provides two relay outputs for under-limit, over-limit and window alarms, plus phase-sequence and phase-unbalance monitoring.
The manual lists input and output specifications, insulation and EMC data, dimensions and DIN-rail mounting instructions, and explains status LEDs, DIP switch and potentiometer configuration, relay operating modes, alarm delay and latching functions, phase-loss/phase-sequence detection, and maintenance notes including an 18-month warranty. This manual is written in Chinese.
| Input signal | Three-phase AC voltage |
|---|---|
| Input voltage range (L-L) | 180~500 VAC |
| Rated input voltage (L-L) | 400 VAC |
| Input frequency | 40~60 Hz |
| Max input voltage (L-L) | 500 VAC |
| Output signal | 2 relays |
| Contact capacity | 5 A / 250 VAC or 30 VDC |
| Measurement accuracy | 3% of UN |
| Alarm modes | Low, high, window alarms, each with latching option |
| Phase unbalance setting range | 5~25%, OFF |
| Delay setting range | 0~10 s |
| Rated insulation voltage | 600 VAC (input-output) |
| Standards | EN 50178; EMC IEC 61326-1; CE |
| Operating temperature | -25°C~+60°C |
| Storage temperature | -40°C~+85°C |
| Relative humidity | 5%~85% RH |
| Housing / dimensions | CH20M housing, 117 x 114 x 22.5 mm (D x H x W) |
| Mounting | DIN 35 mm rail |
It supports low-limit, high-limit and window alarms, each also available with latching (低限报警+锁定, 高限报警+锁定, 窗口报警+锁定).
All ACT20P series isolators are mounted on a DIN 35 mm rail: hook the upper end onto the rail and push the lower end in.
Quality problems occurring during normal use within 18 months from the shipping date are repaired free of charge by the manufacturer.
Yes, DIP switch SW2 sets whether the two relays operate independently or simultaneously.