Weidmuller ACT20P-VMR-3PH-ILP-H Three-Phase AC Voltage Monitoring Relay User Manual

The Weidmuller voltage monitoring module ACT20P- VMR- 3PH- I LP- H is a three-phase AC voltage relay with overvoltage, undervoltage, asymmetry, phase sequence and frequency monitoring functions, and has relay outputs and analog outputs.


Weidmuller ACT20P-VMR-3PH-ILP-H Three-Phase AC Voltage Monitoring Relay User Manual - cover page
Brand
Weidmüller
Category
Voltage and Current Measurement
Document type
User Manual
Language
Chinese
Pages
1
File format
PDF
File size
1.7 MB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
F48A2DC5C0266E6D71EE29B666A41359

About this manual

This document is the Chinese user manual (使用说明书) for the Weidmüller ACT20P-VMR-3PH-ILP-H three-phase AC voltage monitoring and alarm relay, order number 7760054165. It monitors three-phase AC voltage signals with an input range of 180–500 VAC and provides two relay outputs for under-limit, over-limit and window alarms, plus phase-sequence and phase-unbalance monitoring.

The manual lists input and output specifications, insulation and EMC data, dimensions and DIN-rail mounting instructions, and explains status LEDs, DIP switch and potentiometer configuration, relay operating modes, alarm delay and latching functions, phase-loss/phase-sequence detection, and maintenance notes including an 18-month warranty. This manual is written in Chinese.

What's inside

  • Input specifications
  • Output specifications
  • Status indicators and parameter setting
  • Dimensions
  • Installation
  • Relay operating mode
  • Delay and latching
  • Phase loss / phase sequence alarm
  • Under-limit, over-limit and window alarms
  • Maintenance

Specifications

Input signalThree-phase AC voltage
Input voltage range (L-L)180~500 VAC
Rated input voltage (L-L)400 VAC
Input frequency40~60 Hz
Max input voltage (L-L)500 VAC
Output signal2 relays
Contact capacity5 A / 250 VAC or 30 VDC
Measurement accuracy3% of UN
Alarm modesLow, high, window alarms, each with latching option
Phase unbalance setting range5~25%, OFF
Delay setting range0~10 s
Rated insulation voltage600 VAC (input-output)
StandardsEN 50178; EMC IEC 61326-1; CE
Operating temperature-25°C~+60°C
Storage temperature-40°C~+85°C
Relative humidity5%~85% RH
Housing / dimensionsCH20M housing, 117 x 114 x 22.5 mm (D x H x W)
MountingDIN 35 mm rail

Frequently asked questions

What alarm modes does the ACT20P-VMR-3PH-ILP-H support?

It supports low-limit, high-limit and window alarms, each also available with latching (低限报警+锁定, 高限报警+锁定, 窗口报警+锁定).

How is the relay mounted?

All ACT20P series isolators are mounted on a DIN 35 mm rail: hook the upper end onto the rail and push the lower end in.

What is the warranty period?

Quality problems occurring during normal use within 18 months from the shipping date are repaired free of charge by the manufacturer.

Can the two relays work independently?

Yes, DIP switch SW2 sets whether the two relays operate independently or simultaneously.

Download PDF (1.7 MB)

More Weidmüller Manuals