The SMD LED Series provides continuous dimming with reverse or forward phase cut dimmers; as low as 5%, depending upon dimmer and low-end trim of the dimmer.
This document is a dimming guide and step-down transformer application note for the HALO SMD Surface LED Downlight series (SMD4, SMD4-DM, SMD6, SMD6-DM). It states that the SMD LED series provides continuous dimming with reverse or forward phase cut dimmers, down to as low as 5% depending on the dimmer and its low-end trim, and includes wiring diagrams for recessed housing and direct mount installations.
The guide lists tested dimmers from Eaton, Lutron, Leviton and Legrand Pass & Seymour with their minimum and maximum dimming percentages, luminaire counts per circuit and start-up times. It also explains the Rapid Start feature, which can cause a momentary flash at low dimmer settings, and describes the H277, H347 and H347200 step-down transformers, including their power consumption and the maximum number of SMD fixtures per transformer-powered circuit.
| Minimum dimming level | As low as 5% depending on dimmer and low-end trim |
|---|---|
| Supply voltage | 120V AC dimmed power |
| H277 transformer rating | 277V to 120V, 300VA, max 16W at full load |
| H347 transformer rating | 347V to 120V, 75VA, max 15W at full load |
| H347200 transformer rating | 347V to 120V, 200VA, max 28W at full load |
| Max SMD4/SMD6 80 CRI fixtures on H277 | 18 |
| Max SMD4/SMD6 80 CRI fixtures on H347 | 4 |
| Max SMD4/SMD6 80 CRI fixtures on H347200 | 12 |
Dimmers with a Rapid Start feature provide a momentary power boost at start-up, which can cause a momentary flash of the LED lighting, more noticeable at low dimmer settings. Eaton's DAL06P, AAL06 and TAL06P dimmers offer adjustment of the Rapid Start feature to reduce this.
The SMD LED series provides continuous dimming with reverse or forward phase cut dimmers, as low as 5% depending on the dimmer and its low-end trim.
They are qualified to drive multiple Halo LED fixtures on a single circuit in Non-IC construction, but installing one transformer per individual LED fixture on a multi-load circuit is not recommended due to the resulting multiple inductive currents.
H277, H347 and H347200 are UL/cUL listed for use with Halo recessed housings H750T, H750TCP, H7T, H7TNB and H7RT.