Consilium Control M Gas External Gas Alarm Panel Module Data Sheet

The Control M Gas is a control panel with a 4.3" graphical colour display used to manage and supervise a gas alarm system.


Consilium Control M Gas External Gas Alarm Panel Module Data Sheet - cover page
Brand
Consilium
Category
Monitoring Equipment
Document type
Datasheet
Language
English
Pages
4
File format
PDF
File size
773 KB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
0D83F168BD6E886E811F07911372540A

About this manual

This data sheet describes the Control M Gas External, a gas alarm panel module (part no. 5103001-03G) from Consilium for the Salwico GS5000 system. The Control M Gas is a control panel with a 4.3" graphical colour display used to manage and supervise a gas alarm system. The External version can be mounted on any flat surface or flush mounted, independently from a gas alarm cabinet.

The module is equipped with communication buses for connecting to the system via a BBE interface RS-485 or BBE interface PB-485 (Power Boost loop), plus a USB 1.1 port for service and maintenance. It features an alarm buzzer, LED status indicators, two configurable inputs and three programmable outputs. The sheet covers terminals and connections, RS-485 termination, indicators and buttons, addressing, and module and mounting dimensions. Operating instructions are in the User Guide and system assembly details in the Installation Manual.

What's inside

  • General Description
  • Features
  • Data (specifications)
  • Indicators and Buttons
  • Addressing
  • Terminals Connections
  • RS-485 Termination
  • Module Dimensions
  • Mounting Dimensions

Specifications

Operating voltage range22-48 VDC
Current consumption (at 24V)92 mA
Ingress protectionIP55
Operating temperature range-5°C to +55°C
Weight620 g
Display4.3", 480×272 pixels, TFT
USB portUSB 1.1 Embedded Host
RS-485 interfaceIsolated
Digital inputs2 digital inputs, 24 VDC, open circuit supervision
Digital outputs3 digital outputs, 24 VDC max. 40 mA, no supervision
Available addresses1 to 10 (address 1 as system master controller)

Frequently asked questions

What system is the Control M Gas External part of?

It is a gas alarm panel module (part no. 5103001-03G) for the Salwico GS5000 system.

How is the Control M Gas External connected to the system?

It connects via BBE interface RS-485 or BBE interface PB-485, and is wired to Terminal M Gas using ribbon cables.

How should the RS-485 bus be terminated?

Termination is made at each end of the bus (first and last module on the RS-485 segment) with a 120 ohm resistor; two resistors are included in delivery.

What address must the Control M Gas External have as a system master controller?

As a system master controller it must have address 1; available addresses are between 1 and 10.

Download PDF (773 KB)