The Premier Elite 1 & 2 zone panels have been designed to meet the requirement of a low cost easy to use fully functional fire alarm control panel. It is available as either a 1 zone panel, or a 2 zone panel. Each version has 2 sounder circuits, and an alarm relay. There is no configuration, simply connect the detectors & sounders and apply power. The Premier Elite range also includes 4,6 and 8 zone panels. These panels are NOT covered in this manual. They have a separate manual.
The Premier Elite 1 and 2 zone fire alarm panel is a low-cost, easy-to-use fully functional fire alarm control panel, available as either a 1 zone or 2 zone version. Each version has 2 sounder circuits and an alarm relay, and the manual covers mains and battery connections, detector and sounder wiring, display and controls, alarm and fault conditions, battery calculation, specifications, maintenance, false alarms and other events.
It is designed to use a 10K end-of-line resistor on detector zones and a 10k end-of-line resistor on each sounder circuit. The manual also describes LED indicators, control buttons, resetting from an alarm, fault finding for supply, zone and sounder circuit faults, and recommended 12 V sealed lead acid battery sizes.
| Zones | 1 or 2 |
|---|---|
| Sounder circuits | 2 |
| Combined sounder rating | 800mA |
| Detector zone end-of-line resistor | 10K |
| Sounder circuit end-of-line resistor | 10k |
| Batteries | 2 x 12 V sealed lead acid (SLA) |
| Recommended battery sizes | 12V 2Ah standard backup, or 12V 7Ah extended backup |
| Mains cable | Fire resisting 3-core cable, 1 mm² to 2.5 mm² |
| Mains fuse | 3A |
| Transformer secondary voltage | 30-34V |
| Mains supply voltage | 230V AC |
| Battery backup voltage | 24V (2 x 12V in series) |
| Compliance | EN54 Parts 2 & 4 |
| Fault behaviour | Non-latching; clear automatically when fixed |
Each version has 2 sounder circuits, along with an alarm relay.
The panel is designed to use a 10K resistor end of line on the detector zones.
The two batteries are wired in series.
Follow the building evacuation procedure and check that everyone has left the building safely, then the responsible person should locate and investigate the alarm area.
After all detectors and manual call points have been returned to normal, turn the key switch to the controls enabled position, press button 1 to stop the sounders, button 2 to silence the buzzer, and button 3 to reset.
No, all faults are non-latching and clear automatically when the fault has been fixed.