Premier Elite 1-2 Zone Fire Alarm Panel Instruction Manual

The Premier Elite 1 & 2 zone panels have been designed to meet the requirement of a low cost easy to use fully functional fire alarm control panel. It is available as either a 1 zone panel, or a 2 zone panel. Each version has 2 sounder circuits, and an alarm relay. There is no configuration, simply connect the detectors & sounders and apply power. The Premier Elite range also includes 4,6 and 8 zone panels. These panels are NOT covered in this manual. They have a separate manual.


Premier Elite 1-2 Zone Fire Alarm Panel Instruction Manual - cover page
Brand
Premier Elite
Category
Monitoring Equipment
Document type
User Manual
Language
English
Pages
15
File format
PDF
File size
269 KB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
E3E797F910C87A721C04CB40342FFC0E

About this manual

The Premier Elite 1 and 2 zone fire alarm panel is a low-cost, easy-to-use fully functional fire alarm control panel, available as either a 1 zone or 2 zone version. Each version has 2 sounder circuits and an alarm relay, and the manual covers mains and battery connections, detector and sounder wiring, display and controls, alarm and fault conditions, battery calculation, specifications, maintenance, false alarms and other events.

It is designed to use a 10K end-of-line resistor on detector zones and a 10k end-of-line resistor on each sounder circuit. The manual also describes LED indicators, control buttons, resetting from an alarm, fault finding for supply, zone and sounder circuit faults, and recommended 12 V sealed lead acid battery sizes.

What's inside

  • Introduction
  • Mains & Battery
  • Detectors & sounders
  • Display & Controls
  • Alarm Condition & Resetting an alarm
  • Fault display & fault-finding
  • Battery Calculation
  • Specifications
  • Log Book
  • MAINTENANCE WORK

Specifications

Zones1 or 2
Sounder circuits2
Combined sounder rating800mA
Detector zone end-of-line resistor10K
Sounder circuit end-of-line resistor10k
Batteries2 x 12 V sealed lead acid (SLA)
Recommended battery sizes12V 2Ah standard backup, or 12V 7Ah extended backup
Mains cableFire resisting 3-core cable, 1 mm² to 2.5 mm²
Mains fuse3A
Transformer secondary voltage30-34V
Mains supply voltage230V AC
Battery backup voltage24V (2 x 12V in series)
ComplianceEN54 Parts 2 & 4
Fault behaviourNon-latching; clear automatically when fixed

Frequently asked questions

How many sounder circuits does each panel version have?

Each version has 2 sounder circuits, along with an alarm relay.

What end-of-line resistor is used on the detector zones?

The panel is designed to use a 10K resistor end of line on the detector zones.

How are the two batteries connected?

The two batteries are wired in series.

What should be done in the event of a fire?

Follow the building evacuation procedure and check that everyone has left the building safely, then the responsible person should locate and investigate the alarm area.

How do you reset the panel from an alarm condition?

After all detectors and manual call points have been returned to normal, turn the key switch to the controls enabled position, press button 1 to stop the sounders, button 2 to silence the buzzer, and button 3 to reset.

Are faults latching?

No, all faults are non-latching and clear automatically when the fault has been fixed.