This manual covers the Shin Hwa SP520 electric valve positioner. It includes safety precautions, product description, installation, air and power connections, adjustment, and troubleshooting.

The document also lists product specifications such as supply air pressure, power current, feedback power voltage, and intrinsic safety parameters. This manual is written in Chinese.

What's inside

  • Safety precautions
  • Product description
  • Installation
  • Air connection
  • Power connection
  • Adjustment
  • Troubleshooting
  • Product specifications

Specifications

Supply air pressure1.4 to 7 kgf/cm2 (140-700 kPa)
Operating power current3.2 to 24 mA
Feedback signal power supply voltage9 to 28 V, not exceeding 30 V
Intrinsic safety main power parametersUi=DC 28V, Ii=93mA, Pi=0.65W, Ci=0.5nF, Li=10μH
Intrinsic safety feedback signal power parametersUi=DC 28V, Ii=93mA, Pi=0.65W, Ci=57.5nF, Li=10μH

Frequently asked questions

What is the supply air pressure range for the SP520?

The supply air pressure range is 1.4 to 7 kgf/cm2 (140-700 kPa).

What power supply does the SP520 use without the feedback option?

It uses DC 4-20 mA, with a minimum operating current of 3.2 mA and a maximum of 24 mA.

What is the feedback signal power supply voltage range?

The feedback signal power supply voltage should be 9-28 V and must not exceed 30 V.

What intrinsic safety parameters are listed for the main power?

The listed parameters are Ui=DC 28V, Ii=93mA, Pi=0.65W, Ci=0.5nF, and Li=10μH.