The VR18 recorder complies with EN61010-1, UL61010C-1 and CSA C22.2 No.24~93.
The VR18 is a paperless recorder with a 6.4-inch wide TFT color LCD with 640 x 480 dot resolution and up to 18 isolated analog input channels. Its rear panel has six expansion slots for I/O cards (analog input, digital output, digital input, analog output and 24 VDC auxiliary power cards), and it has a standard Ethernet interface with optional RS232/422/485. Measured and configuration data are stored on a CF card (512 MB supplied) in addition to 16 MB of internal memory, and the unit samples at 200 ms.
The operation manual covers safety symbols and precautions, fuse replacement, installation and wiring of the I/O and communication cards, and the basic operating pages (Page, Mode, History, Event, Status, Exit, Dump, Clear, Operate and Shutdown). It then describes configuration of channels, screens, tools, device settings and date/time, the optional password and FDA 21 CFR Part 11 functions, and the Observer 1 & 2 PC software with Ethernet, serial and CF card configuration. Application examples and a question-and-answer chapter close the document. This manual is written in Chinese.
| Display | 6.4-inch wide TFT color LCD, 640 x 480 dots |
|---|---|
| Analog input channels | Up to 18 isolated points |
| Sampling rate | 200 ms |
| A/D resolution | 18-bit analog input |
| Expansion slots | 6 slots on the rear panel |
| Depth | 174 mm |
| Standard communication | Ethernet IEEE 802.3 10 Base T; RS232/422/485 optional |
| Digital output card contacts | 6 relay contacts, 5 A/240 VAC |
| Standard CF card | 512 MB supplied |
| Fuse for 90~250 VAC supply | 2.5 A / 250 VAC time-lag (slow-blow) |
It has a 6.4-inch wide TFT color LCD with a 640 x 480 dot matrix resolution.
Up to 18 isolated analog input channels, using single-, two- or three-channel analog input cards.
The sampling rate is 200 milliseconds.
A 2.5 A / 250 VAC time-lag (slow-blow) fuse; the 11~18 VDC and 18~36 VDC versions use 5.0 A / 250 VAC.