Guoce Huaneng GHC-9600 Transformer Oil Gas Chromatograph Product Technical Manual

GHC-9600 Transformer Oil Gas Chromatograph adopts the three-detector process recommended by national standards, and can complete the full analysis of the content of dissolved gas components (including hydrogen, oxygen, methane, ethylene, ethane, acetylene, carbon monoxide and carbon dioxide) in the insulating oil with one injection.


Guoce Huaneng GHC-9600 Transformer Oil Gas Chromatograph Product Technical Manual - cover page
Brand
Guoce Huaneng
Category
Analyzers
Document type
Product Leaflet
Language
Chinese
Pages
6
File format
PDF
File size
390 KB
Published
10 November, 2023
Updated
10 November, 2023
MD5 checksum
672006516E749F6A7ABB6162E7C58BCC

About this manual

The GHC-9600 is an oil chromatograph analyzer for power systems produced by Wuhan Guoce Huaneng Electric Co., Ltd. (武汉国测华能电气有限公司). Following the national-standard three-detector flow, a single injection completes the full analysis of gases dissolved in insulating oil — hydrogen, oxygen, methane, ethylene, ethane, acetylene, carbon monoxide and carbon dioxide — which generation and supply utilities use to detect hidden overheating or discharge faults in oil-filled equipment. The system also determines the gas content of insulating oil, with a flow design that complies with the power industry standard DL/T 703-1999.

A high-sensitivity thermal conductivity detector, a hydrogen flame ionization detector and a nickel catalyst conversion furnace enable measurement of nine gas components, including nitrogen. The manual lists the instrument configuration (chromatograph mainframe with FID and TCD detectors, conversion furnace, dedicated workstation, shaker, gas sources, standard gases and accessories), the technical parameters, and features such as networked data transmission with remote control and diagnosis, a 5.7-inch LCD switchable between Chinese and English, carrier-gas failure protection for the TCD, 0.1°C four-channel temperature control, self-diagnosis and anti-pollution chromatographic columns. This manual is written in Chinese.

What's inside

  • Analysis of dissolved gases in insulating oil
  • Determination of gas content in insulating oil
  • Instrument configuration
  • Technical parameters
  • Instrument performance and features
  • Typical chromatograms

Specifications

Sample volume1 mL per injection
Minimum detection concentrationH2 2, O2 10, N2 20, CO 1, CO2 5, CH4 0.1, C2H4 0.1, C2H6 0.1, C2H2 0.1 μL/L
DetectorsTCD and FID with nickel catalyst conversion furnace
Ambient temperature0°C to 40°C
Temperature control rangeRoom temperature +5°C to 400°C
Temperature control accuracy±0.1°C
Stabilization timeUnder 30 min
Power1.9 kW
Dimensions660 × 550 × 585 mm
Display5.7-inch LCD, 13 lines, Chinese/English switchable

Frequently asked questions

Which gases can the GHC-9600 measure in transformer oil?

It measures nine dissolved gas components: hydrogen, oxygen, nitrogen, carbon monoxide, carbon dioxide, methane, ethane, ethylene and acetylene.

What detectors does the GHC-9600 use?

It uses a high-sensitivity thermal conductivity detector (TCD) and a hydrogen flame ionization detector (FID), plus a nickel catalyst conversion furnace.

What standard does the GHC-9600 comply with?

Its flow design complies with the Chinese power industry standard DL/T 703-1999 for gas chromatographic determination of gas content in insulating oil.

How much sample is needed for one analysis?

One injection of 1 mL completes the full analysis of the dissolved gas components.