Beiyuan BM5 Series Plastic Case Circuit Breaker User Manual

BM5 series plastic case circuit breakers have the advantages of modularization, small size, high breaking capacity, short arc, high reliability, good environmental protection and comprehensive functions.


Beiyuan BM5 Series Plastic Case Circuit Breaker User Manual - cover page
Brand
Beiyuan
Category
switch
Document type
User Manual
Language
Chinese
Pages
16
File format
PDF
File size
1.8 MB
Published
10 November, 2023
Updated
10 November, 2023
Model
BM5
MD5 checksum
A6056174233869A002ECE81371A022EC

About this manual

This manual covers the Beiyuan BM5 series plastic case circuit breakers for AC 50/60 Hz circuits, with rated insulation voltage AC1000 V, rated working voltage AC400 V/AC690 V and rated current up to 630 A. It describes L, M, H and S short-circuit breaking capacity levels, normal operating conditions, specifications and applicable standards.

The document also details internal and external accessories such as shunt trips, undervoltage releases, auxiliary and alarm contacts, electric and manual operating mechanisms, outline and installation dimensions, and use and maintenance instructions. This manual is written in Chinese.

What's inside

  • Scope of application
  • Model designation and meaning
  • Normal operating conditions
  • Specifications
  • Internal accessories
  • External accessories
  • Outline and installation dimensions
  • Use and maintenance

Specifications

Rated insulation voltageAC1000 V
Rated working voltageAC400 V / AC690 V
Rated currentUp to 630 A
Frequency50/60 Hz
Rated operating short-circuit breaking capacity at AC400 V85/100/150 kA (L/M/H)
Rated operating short-circuit breaking capacity at AC690 V15/20/25 kA and 20/30/40 kA
Electrical life at AC400 V10000 operations
Auxiliary contact thermal current3 A
Shunt trip release control voltageAC 230 V or 400 V; DC 24 V
Electric operator operation frequencyNo more than 180 operations per hour for 160/250 A frames

Frequently asked questions

What is the rated insulation voltage of the BM5 circuit breaker?

The manual states a rated insulation voltage of AC1000 V.

What ambient temperature range is specified for normal use?

Normal use is up to 40°C, with a 24-hour average not above 35°C and a lower limit of -5°C.

What is the maximum operating frequency of the electric mechanism for 160/250 A frames?

No more than 180 operations per hour.

When can a breaker with an undervoltage release be opened or closed normally?

It can be opened or closed normally only when the control voltage is at least 85% of Us.