This document describes the installation and operation of the FTA1100 diesel engine fire pump controller.
This guide covers the installation and operation of the Firetrol FTA1100, a combined automatic and manual diesel engine fire pump controller intended for starting and monitoring fire pump diesel engines. It explains the catalog number structure (model, battery type, battery voltage and incoming voltage) and describes the available methods of starting and stopping, including automatic start on low pressure, manual crank, remote manual and automatic start, sequential start, flow/zone start, weekly start and test start.
Installation sections give requirements for controller location, working clearances, ambient temperature, enclosure rating and mounting, including a wall mount procedure and the tools and materials needed. The document also lists the controller's UL, CSA and Factory Mutual listings, NFPA references, seismic testing standards and FCC/Industry Canada radio compliance statements.
| Battery voltage | 12 V or 24 V |
|---|---|
| Battery type | Lead acid (L) or Nickel-Cadmium (N) |
| Incoming voltage | Standard 110/120 V 50/60 Hz; option -BA 208/240 V 50/60 Hz |
| Standard enclosure rating | NEMA 2 |
| Pump room ambient temperature | 39°F (4°C) to 104°F (40°C) |
| Minimum height of current carrying parts | 12 in. (305 mm) above floor level |
| Listings | UL218, cUL (CSA), Factory Mutual |
| Seismic test standards | ICC-ES AC156, IBC 2015 and CBC 2016 |
| RF exposure separation distance | At least 20 cm from the antenna |
The engine can be started by pressing the CRANK 1 and/or CRANK 2 push button when the Main Selector switch is in the HAND position.
It is available for 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries.
The emergency stop is always possible in any running condition and is done by positioning the main selector switch to the OFF position.
The pump room ambient temperature shall be between 39°F (4°C) and 104°F (40°C), unless a temperature option is included.