The PS-1000 Analog Transmitter is ideal for use on systems having a full scale range of 10 mV, 20 mV, or 30 mV with minimal tare weight values. Typical applications would be a single force or pressure transducer, or a platform scale.
PS-1000 analog transmitters are intended for systems with a full scale range of 10 mV, 20 mV, or 30 mV, such as a single force or pressure transducer or a platform scale. The unit has a 9-position terminal strip for supply, transducer, and analog output connections; input range is selected with SW1, output signal with jumpers JP1, JP2, or JP3, and zero and span are set with trim pots.
The manual covers general information, specifications, wiring connections, calibration, analog output selection, and input signal selection. It also describes the optional 24 Vdc PS-121 power supply for 230 Vac operation, including installation and fuse replacement.
| Power Supply | 24 Vdc + 15% |
|---|---|
| Power Consumption | 5 Watts |
| Load Cell Excitation | 10 Vdc |
| Load Current | 200 mA (4 load cells x 350 Ω) |
| Input Signal | Selectable, 10 mV, 20 mV, 30 mV |
| Voltage Output | 0-10 Vdc (2 kΩ min load) |
| Current Output | 4-20 mA (500 Ω load max) |
| Operating Temperature Range | -10 to +40°C |
| Dimensions | 76x90x65 mm |
| Mounting | DIN-Rail mount |
| Material | ABS Plastic |
| Weight | 120g |
The input signal is selectable between 10 mV, 20 mV, and 30 mV.
It is mounted horizontally on DIN-Rail with terminal block TB1 positioned on the bottom.
The optional 24 Vdc power supply enables the PS-1000 to be operated with 230 Vac.
The cable between the two devices must not exceed 1 meter.