This document is about the user and maintenance manual for the UV/IR Flame Detector UV/IR - Model ZT-20EX.
The GLT Exports ZT-20EX is a UV/IR flame detector intended for Ex/hazardous areas. It uses dual-spectrum UV and IR channels and microprocessor-based digital signal processing to sense fire and flames and activate an alarm or extinguishing system directly or through a control circuit.
This user and maintenance manual describes the detector's technical description, performance, operation, specifications, installation, operating instructions, maintenance, troubleshooting, and typical wiring configurations. It also includes certification instructions and ordering information.
| Operating voltage | Nominal 24 VDC (17–31 VDC) |
|---|---|
| Power consumption | Max. 35 mA in standby; max. 75 mA in alarm |
| IR detector centre wavelength | 4.35 microns |
| UV detector pass band | 185 to 260 nanometres |
| Field of view | Horizontal 90°; vertical 90° |
| Detection range | Nom. 30 m at 30 x 30 cm heptane fire |
| Operating temperature range | -40°C to +75°C (-40°F to +167°F) |
| Humidity range | 0 to 95% RH non-condensing |
It is nominally 30 m for a 30 x 30 cm heptane fire.
It uses nominal 24 VDC and operates from 17 to 31 VDC.
Both the horizontal and vertical fields of view are 90°.
The detector operates from -40°C to +75°C.